Specifications, Voltage sensing input, Power supply – Basler Electric BE1-47N User Manual
Page 11: Target indicators, Negative sequence voltage

9170400990 Rev J
BE1-47N General Information
1-3
Specifications
BE1-47N electrical and physical specifications are listed in the following paragraphs.
Voltage Sensing Input
Voltage
Nominal:
120 or 208 Vac (60 Hz)
100 or 173 Vac (50 Hz)
Maximum Continuous:
160% of nominal
Frequency
Nominal:
50 or 60 Hz (dictated by relay style)
Range
50 Hz Sensing Input:
45 to 55 Hz
60 Hz Sensing Input:
55 to 65 Hz
Burden:
≤
2 VA per phase
Power Supply
Power supply types and specifications are listed in Table 1-1.
Table 1-1. Power Supply Ratings
Type
Nominal
Input Voltage
Input Voltage
Range
Burden at Nominal
O (midrange)
48 Vdc
24 to 150 Vdc
4.6 W
P (midrange)
125 Vdc
24 to 150 Vdc
4.6 W
120 Vac
90 to 132 Vac
17.5 VA
R (low range)
24 Vdc
12 to 32 Vdc ∗
4.6 W
S (midrange)
48 Vdc
24 to 150 Vdc
4.6 W
125 Vdc
24 to 150 Vdc
4.6 W
T (high range)
250 Vdc
68 to 280 Vdc
4.6 W
240 Vac
90 to 270 Vac
24.4 VA
∗
Type R power supply initially requires 14 Vdc to begin operating. Once operating, the input
voltage may be reduced to 12 Vdc and operation will continue.
Target Indicators
Electronically latched, manually reset target indicators are optionally available to indicate closure of the
trip output contacts. Either internally operated or current operated targets may be specified. Internally
operated targets should be selected when normally-closed (NC) output contacts are specified.
Current Operated Targets
Minimum Rating ......................... 200 mA flowing through the trip circuit
Continuous Rating ...................... 3 A
1 Second Rating ......................... 30 A
2 Minute Rating .......................... 7 A
Negative Sequence Voltage
Pickup
Setting Range ............................ 2 to 32% of nominal
Increment ................................... 2%
Accuracy .................................... ±1 unit of the percent setting of the negative sequence voltage at
nominal frequency (50 or 60 Hz as defined by the style number)
Dropout ............................................. 98% of pickup