Output contacts, Type tests, Physical – Basler Electric BE1-47N User Manual
Page 13: Agency recognition/certification

9170400990 Rev J
BE1-47N General Information
1-5
Output Contacts
Resistive Ratings
120 Vac ...................................... Make, break, and carry 7 Aac continuously
250 Vdc ...................................... Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
500 Vdc ...................................... Make and carry 15 Adc for 0.2 s, carry 7 Adc continuously,
break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc ....... Break 0.3 A (L/R = 0.04)
Type Tests
Shock ................................................ Withstands 15 G in each of three mutually perpendicular planes
without structural damage or performance degradation.
Vibration ............................................ Withstands 2 G in each of three mutually perpendicular planes,
swept over the range of 10 to 500 Hz for a total of six sweeps, 15
minutes each sweep, without structural damage or degradation of
performance.
Dielectric Strength ............................ Tested in accordance with IEC 255-5 and IEEE C37.90
All circuits to ground ......... 2,121 Vdc applied for 1 min
Input to output circuits ...... 1,500 Vac or 2,121 Vdc applied for 1 min
Radio Frequency Interference .......... Maintains proper operation when tested for interference in
accordance with IEEE C37.90.2-1987, Standard Withstand
Capability of Relay Systems to Radiated Electromagnetic
Interference from Transceivers.
Surge Withstand Capability .............. Qualified to IEEE C37.90.1-1989, Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay Systems.
Fast Transient ................................... Qualified to IEEE C37.90.1-1989
Impulse ............................................. Qualified to IEC 255-5
Physical
Temperature
Operating Range ........................ –40 to 70°C (–40 to 158°F)
Storage Range ........................... –65 to 100°C (–85 to 212°F)
Weight ............................................. 14 lb (6.35 kg)
Case Size ......................................... S1 (Refer Section 4 for case dimensions.)
Agency Recognition/Certification
UL Recognition ................................. UL recognized per Standard 508, File E97033
NOTE: Output contacts are not UL recognized for voltages greater
than 250 volts.
GOST-R Certification ........................ GOST-R certified per the relevant standards of Gosstandart of
Russia.