3 • functional description, Introduction, Voltage sensing – Basler Electric BE1-47N User Manual
Page 17: Section 3, Functional description -1

9170400990 Rev J
BE1-47N Functional Description
3-1
SECTION 3 • FUNCTIONAL DESCRIPTION
Introduction
BE1-47N relay functions are illustrated in Figure 3-1 and described in the following paragraphs.
Figure 3-1. Function Block Diagram
Voltage Sensing
One of two nominal voltage levels may be specified for a system frequency of 50 hertz or 60 hertz.
Voltage sensing input options are summarized in Table 3-1.
Table 3-1. Voltage Sensing Input Options
Sensing Input Option
Nominal Voltage
Frequency
3
120 Vac
60 Hz
4
100 Vac
50 Hz
5
208 Vac
60 Hz
6
173 Vac
50 Hz
Three-phase system voltage is supplied to internal potential transformers (PTs). These PTs are an
integral part of the sequence filter and provide isolation, step-down scaling, and phasor summation to
eliminate the zero-sequence component of the sensed voltages.