Basler Electric BE1-51/27R User Manual
Page 9

9137200999 Rev F
3
Multiple of
Setting
Multiple of
Pickup
Time Dial Setting (Seconds)
00
01
02
03
05
07
10
1.50
6.00
0.159
0.220
0.285
0.347
0.474
0.599
0.790
1.75
7.00
0.151
0.204
0.263
0.320
0.435
0.553
0.727
2.00
8.00
0.142
0.191
0.246
0.300
0.412
0.520
0.683
2.25
9.00
0.136
0.185
0.240
0.290
0.939
0.499
0.654
2.50
10.00
0.130
0.180
0.227
0.277
0.372
0.477
0.622
3.00
12.00
0.123
0.170
0.215
0.262
0.355
0.453
0.593
3.50
14.00
0.118
0.163
0.208
0.250
0.341
0.433
0.566
4.00
16.00
0.117
0.159
0.201
0.243
0.329
0.420
0.548
4.50
18.00
0.112
0.153
0.195
0.237
0.322
0.406
0.537
5.00
20.00
0.111
0.154
0.188
0.231
0.316
0.400
0.526
Table 3. Timing, Curve B4, BE1-51/27R at 25% Voltage (20 to 99 Time Dial Settings)
Multiple of
Setting
Multiple of
Pickup
Time Dial Setting (Seconds)
20
30
40
50
60
80
99
0.38
1.50
5.671
8.222
10.788
13.344
15.919
20.918
25.707
0.43
1.70
4.533
6.556
8.527
10.662
12.694
16.698
20.464
0.50
2.00
3.593
5.207
6.808
8.407
9.986
13.164
16.276
0.55
2.20
3.198
4.636
6.041
7.482
8.906
11.694
14.486
0.63
2.50
2.766
4.003
5.218
6.454
7.682
10.146
12.453
0.68
2.70
2.569
3.720
4.848
5.986
7.130
9.381
11.557
0.75
3.00
2.322
3.358
4.372
5.409
6.434
8.489
10.454
0.88
3.50
2.026
2.931
3.829
4.726
5.627
7.406
9.120
1.00
4.00
1.833
2.647
3.450
4.258
5.076
6.688
8.214
1.13
4.50
1.691
2.438
3.188
3.932
4.673
6.166
7.597
1.25
5.00
1.464
2.117
2.749
3.380
4.022
5.303
6.513
1.50
6.00
1.424
2.060
2.688
3.314
3.949
5.200
6.396
1.75
7.00
1.318
1.897
2.479
3.060
3.644
4.802
5.899
2.00
8.00
1.234
1.792
2.329
2.884
3.430
4.518
5.561
2.25
9.00
1.184
1.704
2.229
2.748
3.273
4.298
5.290
2.50
10.00
1.120
1.604
2.093
2.589
3.070
4.053
4.977
3.00
12.00
1.073
1.551
2.018
2.498
2.971
3.917
4.817
3.50
14.00
1.028
1.481
1.928
2.390
2.841
3.741
4.603
4.00
16.00
0.989
1.430
1.866
2.304
2.741
3.610
4.443
4.50
18.00
0.958
1.392
1.818
2.243
2.667
3.514
4.328
5.00
20.00
0.944
1.372
1.786
2.200
2.619
3.454
4.252
BE1-51/27R
Introduction