Basler Electric BE1-51/27R User Manual
Page 74

68
9137200999 Rev F
Table 10. Timing Curve Selection Table
Timing Type
Selector
Position
Z1, Z3
Selector
Position
Z2
Standard
Curves
Z1, Z2
Fig. No.
Extended
Curves
Z1, Z2
Fig. No.
Standard
Curves
Z3
Fig. No.
Extended
Curves
Z3
Fig. No.
B1 - Short Inverse
3
3
A-1
A-2
A-38
A-39
B2 - Long Inverse
1
1
A-3
A-4
A-40
A-41
B3 - Definite Time
5
5
A-5
A-6
A-42
A-43
B4 - Moderately Inverse
2
2
A-7
A-8
A-44
A-45
B5 - Inverse
4
4
A-9
A-10
A-46
A-47
B6 - Very Inverse
6
6
A-11
A-12
A-48
A-49
B7 - Extremely Inverse
7
7
A-13
A-14
A-50
A-51
B8 - I
2
t
0
0
A-15
A-16
A-52
A-53
C1 - I
2
t with Limit #1
8
—
A-17
A-18
A-54
A-55
C2 - I
2
t with Limit #2
9
—
A-19
A-20
A-56
A-57
C3 - I
2
t with Limit #3
A
—
A-21
A-22
A-58
A-59
C4 - I
2
t with Limit #4
B
—
A-23
A-24
A-60
A-61
C5 - I
2
t with Limit #5
C
—
A-25
A-26
A-62
A-63
C6 - I
2
t with Limit #6
D
—
A-27
A-28
A-64
A-65
C7 - I
2
t with Limit #7
E
—
A-29
A-30
A-66
A-67
C8 - I
2
t with Limit #8
F
—
A-31
A-32
A-68
A-69
E2 - Long Inverse
—
8
A-33
—
—
—
E4 - Inverse
—
9
A-34
—
—
—
E5 - Inverse
—
A
A-35
—
—
—
E6 - Very Inverse
—
B
A-36
—
—
—
E7 - Extremely Inverse
—
C,D,E,F
A-37
—
—
—
Time Overcurrent Characteristic Curves
BE1-51/27R