Target indicators, Power supply, Radio frequency interference (rfi) – Basler Electric BE1-51/27R User Manual
Page 71: Isolation, Surge withstand capability, Ul recognized, Gost-r, Operating temperature

9137200999 Rev F
65
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc........ Break 0.3 A (L/R = 0.04)
Target Indicators
Function targets may be specified as either internally operated or current operated by a minimum of 0.2
amperes through the output trip circuit. When current operated, the output circuit must be limited to 30
amperes for 0.2 seconds, 7 amperes for 2 minutes, and 3 amperes continuously.
Power Supply
Power for the internal circuitry may be derived from a variety of ac or dc external power sources as
indicated in Table 8.
Table 8. Power Supply Specifications
Type
Input Voltage
Burden at Nominal
Nominal
Range
O (mid-range)
48 Vdc
24 to 150 Vdc
1.6 W
P (mid-range)
125 Vdc
120 Vac
24 to 150 Vdc
90 to 132 Vac
1.9 W
8.9 VA
R (low-range)
24 Vdc
12 to 32 Vdc
*
1.7 W
S (mid-range)
48 Vdc
125 Vdc
24 to 150 Vdc
24 to 150 Vdc
1.6 W
1.9 W
T (high-range)
250 Vdc
240 Vac
68 to 280 Vdc
90 to 270 Vac
2.1 W
14.2 VA
* Type R power supply may require 14 Vdc to begin operation. Once operating, the voltage may be
reduced to 12 Vdc.
Radio Frequency Interference (RFI)
Field-tested using a five-watt, hand-held transceiver operating at random frequencies centered around
144 MHz and 440 MHz, with the antenna located six inches from the relay in both horizontal and vertical
planes.
Isolation
In accordance with IEC 255-5 and ANSI/IEEE C37.90, one-minute dielectric (high potential) tests as
follows:
All circuits to ground ........................ 2,121 Vdc
Input to output circuits ..................... 1,500 Vac or 2,121 Vdc
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989, Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems.
UL Recognized
UL recognized per Standard 508, UL File No. E97033. Note: Output contacts are not UL recognized for
voltages greater than 250 volts and input power supply voltages greater than 150 volts.
GOST-R
GOST-R certified per the relevant standards of Gosstandart of Russia.
Operating Temperature
The operating temperature range is from
−40°C (−40°F) to +70°C (+158°F).
BE1-51/27R
Specifications