Fireplace insert installation, Insert placement requirements, Ql p o m – Avalon Firestyles Small Flush Hybrid-Fyre User Manual
Page 9: Nk s x

Fireplace
Insert
Installation
(for qualified installers only)
9
© Travis Industries
100-01342
4150521
Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert (item “q” below).
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements listed below must be met.
Minimum Clearances
k Sidewall
11.625" 296mm
l Side Facing (non-combustible)
6.25" 159mm
m Top Facing (non-combustible)
37.5" 953mm
n Mantel (combustible – maximum 12” 305mm deep)
37.5" 953mm
o Front Hearth
16” 407mm
(USA)
18” 458mm
(Canada)
p Side Hearth
8" 204mm
q Front of Insert
36" 915mm
s Mantel Column (max. 8” 204mm deep)
6.25" 159mm
x Extension Onto Hearth
1.5" 39mm
Combustible Top Facing
Side
Wall
Non-Combustible
Hearth
Facing
q
l
p
o
m
Combustible Mantel
n
k
s
x