Reboot the Shelf Manager or restart the HPI daemon with sv_stop and sv_start
commands in order to activate the modified configuration. Assure that the active Shelf
Manager works with the modified configuration file.

Table 4-42 Parameters of Cooling System

Parameter Name

Default Value

Description

OPENHPI_LOG_DEBUG_FACILITIES

“”

"ipmicooling" enables logging. It enables
the shelf manager to log the cooling
related information into files
/var/log/bbs-hpib0X.log

where

X

can be in the range of 0 to

OPENHPI_LOGFILE_MAX

as

mentioned in the /etc/bbs-
hpib/bbs-hpib.conf

configuration

file.

Cooling_DeactOnUpperNonRecov

erTemp

“1”

Enables the function to power off all
blades and drop fan speed after
receiving upper non recoverable (UNR)
thermal events from two different
resources in the C2000 R3.0 shelf.

Cooling_FanMinimumLevel

“12|15”

Default fan speed in %.
12 - default value for C2000 R3.0 shelfs.
15 - default value for the other shelfs.

Cooling_InletOutletLowerTemp

erature

“20”

Lower temperature point for inlet/outlet
control

Cooling_InletOutletUpperTemp

erature

“40”

Upper temperature point

Cooling_InletOutletLowerSetP

oint

“10”

Set point at upper temperature

Cooling_InletOutletUpperSetP

oint

“25”

Set point at lower temperature Range 25
to 15, most effect at 15. Influences the
difference between in- and outlet
temperature.

Cooling_InltOutltMinimumSens

orTemperature

“18”

Below this inlet temperature the
inlet/outlet related control is disabled