Table 4-42, Parameters of cooling system, Using hpi-b – Artesyn System Management Interface Based on HPI-B (Centellis 2000 R3.0/4411) User's Guide (June 2014) User Manual
Page 79

Using HPI-B
System Management Interface Based on HPI-B (Centellis 2000 R3.0/4411) User’s Guide (6806800P20C)
79
Reboot the Shelf Manager or restart the HPI daemon with sv_stop and sv_start
commands in order to activate the modified configuration. Assure that the active Shelf
Manager works with the modified configuration file.
Table 4-42 Parameters of Cooling System
Parameter Name
Default Value
Description
OPENHPI_LOG_DEBUG_FACILITIES
“”
"ipmicooling" enables logging. It enables
the shelf manager to log the cooling
related information into files
/var/log/bbs-hpib0X.log
where
X
can be in the range of 0 to
OPENHPI_LOGFILE_MAX
as
mentioned in the /etc/bbs-
hpib/bbs-hpib.conf
configuration
file.
Cooling_DeactOnUpperNonRecov
erTemp
“1”
Enables the function to power off all
blades and drop fan speed after
receiving upper non recoverable (UNR)
thermal events from two different
resources in the C2000 R3.0 shelf.
Cooling_FanMinimumLevel
“12|15”
Default fan speed in %.
12 - default value for C2000 R3.0 shelfs.
15 - default value for the other shelfs.
Cooling_InletOutletLowerTemp
erature
“20”
Lower temperature point for inlet/outlet
control
Cooling_InletOutletUpperTemp
erature
“40”
Upper temperature point
Cooling_InletOutletLowerSetP
oint
“10”
Set point at upper temperature
Cooling_InletOutletUpperSetP
oint
“25”
Set point at lower temperature Range 25
to 15, most effect at 15. Influences the
difference between in- and outlet
temperature.
Cooling_InltOutltMinimumSens
orTemperature
“18”
Below this inlet temperature the
inlet/outlet related control is disabled