4.6. Configuration of the PEF 150 module
PEF150 is interface for control up to 64 dimmable ballasts for fluorescent lamps on one bus divided up
to 15 independent groups.
Fig. 16
4.6.1. PEF 150 parameters description
• Interface address address of the module. The addresses of both channels of this module are
based on this value.
• Bank 0-9 module group
• Filter 0-180 msec. Minimum time of pressing the button for the press to be valid.
• Long press 0-900 msec. If the time of pressing the button is longer than this value, the press is
interpreted as a long press.
The followingparameters can be set for the first and second channel independently. These channels
can be controlled by buttons. The number of channels equals the number of controlled DALI groups.
• Function mode selection for control dimmers by its buttons
− no action - buttons are disabled.
− toggle - switch outputs between maximum and minimum values.
− solid state - if no button is pressed, the output has the minimum value. If one button is
pressed, the output has the value entered in the parameter Intermediate. If both buttons are
pressed, the output has the maximum value.
− dimmer – a short press of the UP/DOWN button changes the output value to
maximum/minimum at the speed set in the parameter Short press fade. A long press makes
the output dim up/down at the speed set in the parameter Long press fade. A release of the
User Manual PEX Software
www.cue.cz
Page 21 of 25