4.4. Configuration of the PEA 208 module
PEA208 is a two-channel analog output 0 - 10V interface for devices with analog control 0 - 10V
(dimmable ballast for fluorescent lamps – Osram, Siemens, Helvar, Philips, dimmers, frequency
converters ...).
Fig. 14
4.4.1. PEA 208 parameters description
• Interface address 0-15 address of the module. The addresses of both channels of this module
are based on this value.
• Bank 0-9 module group
• Filter 0-180 msec. Minimum time of pressing the button for the press to be valid.
• Long press 0-900 msec. If the time of pressing the button is longer than this value, the press is
interpreted as a long press.
The following parameters can be set for each channel independently:
• Function mode selection for control dimmers by it’s buttons
− no action - buttons are disabled.
− toggle - switch outputs between maximum and minimum values.
− solid state - if no button is pressed, the output has the minimum value. If one button is
pressed, the output has the value entered in the parameter Intermediate. If both buttons are
pressed, the output has the maximum value.
− dimmer – a short press of the UP/DOWN button changes the output value to
maximum/minimum at the speed set in the parameter Short press fade. A long press makes
the output dim up/down at the speed set in the parameter Long press fade. A release of the
button makes it stop at the currently reached value.
− fluorescent – a short press of the UP/DOWN button changes the output value to
maximum/minimum at the speed set in the parameter Short press fade. A long press makes
the output dim up/down at the speed set in the parameter Long press fade. A release of the
User Manual PEX Software