Advanced programming – CP Electronics VITP-MWS3A User Manual
Page 6
6
Parameter Name Default Value Range / Options Description
UHS5 UNLCDHS
Detector Parameters
Walk Test LED
Off
On or Off
When set to On this causes a red LED to flash on the sensor when it detects
movement. Use this feature to check for adequate sensitivity levels.
Time Out
(Time adjustment)
20 minutes
0-99 minutes
Once the detector is turned on, this value sets how long the lights will stay on once
movement has ceased. Select 0 for 10 second delay – use for commissioning only.
Sensitivity On
9
1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is already on. *UHS5
sets Sensitivity On and Off to the same value.
*
Sensitivity Off
9
1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is off. *UHS5 sets
Sensitivity On and Off to the same value.
*
Lux time
0
0 (disabled)
1-99 minutes
If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
timed delay the lux change reverses then the process is cancelled.
Power Up State
On
On or Off
Select No for a 30 second delay on start up. If Yes is selected, there will be no
delay on start up and the detector will always power up detecting.
Factory default
-
-
Restores factory default settings
User Modes
Raise
-
-
Increase light level. Reverts when occupancy cycle complete.
Lower
-
-
Decrease light level. Reverts when occupancy cycle complete.
Override On
-
-
If the lights are off, sending the IR command will turn them on immediately and
revert to automatic operation using the manual timeout period.
Override Off
-
-
If the lights are on, sending the IR command will turn them off immediately. After
the manual timeout period (described above), the sensor will revert to automatic.
Cancel
-
-
Cancels the on or off override, returning the detector to normal operation.
Advanced programming