12

Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.

Dimensions

See diagrams opposite

Weight

0.15kg

Supply Voltage

230VAC +/- 10%

Frequency

50Hz

Maximum Load

Channel 1 (switching):
10A of lighting and/or ventilation

including incandescent, fluorescent,
compact fluorescent, low voltage (by
switching the primary of transformer).

Channel 2 (dimming):
Maximum number of DSI or DALI
ballasts is 10 unless the relay is
disabled then it is 20.

Power consumption

On 1100mW, Off 664mW


Dimming output

Basic insulation only. Although low
voltage, this is not an SELV output
and should be treated as if mains
potential. Use mains rated wiring.

Terminal Capacity

2.5mm

2

Temperature

-10ºC to 50ºC

Humidity

5 to 95% non-condensing

Material (casing)

Flame retardant ABS and PC/ABS

Type

Class 2


Microwave frequency 5.8 GHz
Safety

The microwave radiation emitted
by these units is extremely low
power and complies with ANSI
standard “IEEEC95.1-1999
Standard for Safety Levels with
Respect to Human Exposure to
Radio Frequency Electromagnetic
Fields 3kHz 300GHz.”


IP rating

IP40

Compliance

EMC-2004/108/EC
LVD-2006/95/EC

Technical data

Part numbers

C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel:

+ 44 (0) 333 900 0671

Fax:

+ 44 (0) 333 900 0674

www.cpelectronics.co.uk
[email protected]

Ref: #WD549 Issue 2

FM 45789

EMS 534520

IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE Wiring
Regulations and any applicable Building Regulations.

MWS6-DD

DBB

Part number

Description

Detector

MWS6-DD

Ceiling microwave presence detector – DALI / DSI dimming

Accessories

DBB

Surface mounting box

UHS5

Programming IR handset

UNLCDHS

Universal LCD IR handset