Do not wire across phases, Wiring – CP Electronics VITM4 (old ceiling rose) User Manual
Page 2
2
Permanent Live
Neutral
Earth
Switched live
Absence detector
Live
Local lighting switch and local emergency test switch
N E
L
Local emergency test
switch
Local lighting
switch
Luminaire connections / Lead colours
Permanent Live Black (4 core only)
Neutral
Blue
Earth
Green / Yellow
Switched Live
Brown
Emergency test using central switch
N E
L
Multiple boxes
Emergency test using power interruption
N E
L
DO NOT WIRE ACROSS
PHASES
Central
emergency
test switch
Wire link
All wiring should be mains rated.
Remove wiring compartment cover.
Wire the box using the diagrams below
Permanent live feeds emergency fittings
Absence detector connects switches through to detectors
Switched live turns the lights on and off
Use the cable clamps to secure the wiring or use cable glands
(not supplied). The clamps can be split, and flipped over to
clamp different cable diameters.
Replace wiring compartment cover.
Plug in the luminaires ensuring that the connector latches to the
box.
Small
cables
Large
cables
Cable clamps
A local lighting switch may still be used when there
is a central emergency test switch or when a circuit
breaker is used to interrupt the power.
Wiring