4 standard types ( three phase 50hz ), 5 overcompensation relay option – CIRCUTOR LCL Series User Manual
Page 5

------ LCL filters: Instructions Manual ----- Page 5
5
Working voltage
< 1,15 of rated U
Transient overload
(10s)
1000 V
Isolation voltage against earth
3 kV
Operating temperature
-25 / +50 ºC
Losses
0,5W/kvar
4.4 Standard Types ( Three phase 50Hz )
TYPE
(1) (3)
RATED
VOLTAGE
(V )
RATED
LOAD
CURRENT
(A
RMS
)
RATED FILTERING
CURRENT
(A
RMS
) (2)
CABINET MODEL
LOSSES
W
LC L35-9A-400
400/415
9
3,6
A
55
LC L35-12A-400
400/415
12
4,8
A
73
LC L35-16A-400
400/415
16
6,4
A
97
LC L35-22A-400
400/415
22
8,8
A
134
LC L35-32A-400
400/415
32
12,8
A
194
LC L35-40A-400
400/415
40
16
A
243
LC L35-47A-400
400/415
47
18,8
B
286
LC L35-54A-400
400/415
54
21,6
B
328
LC L35-64A-400
400/415
64
25,6
B
389
LC L35-76A-400
400/415
76
30,4
B
462
LC L35-90A-400
400/415
90
36
B
547
LC L35-110A-400
400/415
110
44
C
668
LC L35-150A-400
400/415
150
60
C
911
LC L35-180A-400
400/415
180
72
C
1094
LC L35-220A-400
400/415
220
88
D
1337
LC L35-260A-400
400/415
260
104
D
1580
LC L35-320A-400
400/415
320
128
D
1944
LC L35-400A-400
400/415
400
160
D
2430
REMARKS
1) If protection against power factor overcompensation is desired, specify in the order
2) Load is supposed to be a three phase 6 pulse rectifier, with dominant harmonics of order 5 and 7
3) For 60 Hz types, specify LCL36 instead of LCL35
4.5 Overcompensation relay option
Measuring instrument
CMM-96-MD
Contactor
suitable for the filter power
Current transformer
TP type