beautypg.com

Earth cable connection, Current transformer (ct) connection – CIRCUTOR OPTIM P&P Series User Manual

Page 13

background image

3.8.- EARTH CABLE CONNECTION

Connect the earth cable to the capacitor bank's earth terminal located on the operating panel

of the unit.

The earth cable cross-section will be selected in accordance with the admissible current limits

established in the LVR (ITC-BT-19 – Internal or receiver installations) for each type of cable and

their location.

3.9.- CURRENT TRANSFORMER (CT) CONNECTION

A current transformer (CT) that is external to the capacitor bank must be

installed to measure the total load current plus that of the capacitor bank

(

Figure 6

).

The standard transformer must have a nominal output of 5 A at the secondary.

We recommend connecting the CT to phase L1 in the direction of the current flow

from P1 to P2 (see

Figure 6

) and connecting the secondary (terminals S1, S2) to

the terminals with the same name on the capacitor bank (see

Figure 6

)

Avoid current flow through the CT primary winding prior to connecting it to termi-

nals S1 S2 of the bank.

If the CT must be installed while the installation is under load, short-circuit S1 and

S2 while they are not connected to the capacitor bank.

The current value of the CT primary winding must be equal to or slightly greater than the size of

the mains switch of the installation. Therefore, the CT must be able to measure the maximum

current expected to be consumed by all the loads being compensated.

Figure 6: Installation of the external current transformer (CT).

The connection point of the CT for a capacitor bank that compensates an entire installation is

after the mains switch of the installation.

To prevent excessive attenuation of the signal, it is recommended that the minimum cross-sec-

tion of the secondary section winding cable (terminals S1, S2) is at least

2.5 mm

2

.

13

Instruction Manual

OPTIM P&P Series