CIRCUTOR REC2C Series (Available until stock) User Manual
CIRCUTOR Measuring instruments

INTERRUPTOR DIFERENCIAL DE RECONEXIÓN AUTOMÁTICA
SEL-RECLOSING RCCB
DESCRIPCIÓN GENERAL
DESCRIPCIÓN LED´s Y MODO REARME .
- Interruptor Diferencial clase A (IEC 1008.1)
- Dispone de sistema de REARME AUTOMÁTICO.
· Modo Control Aislamiento.
· Modo Secuencia Tiempo.
- Montaje en Carril DIN 46277 (EN 50022)
- Led verde.
· OFF, REConexión MANUAL
· ON, REConexión AUTOMÁTICA
- con párpadeo rápido, indica un cambio en el
modo de reconexión.
- Led rojo.
· OFF, Interruptor diferencial no disparado.
· ON , Interruptor diferencial disparado.
- con párpadeo lento, temporiza la secuencia
de reconexión.
- con parpadeo rápido, realiza test de aislamiento.
- fijo, agotada las temporizaciones y secuencias,
queda bloqueado.
- Modo rearme.
· Mediante control de aislamiento, conmutador arriba M
· Mediante secuencia de tiempos, conmutador abajo
T
-
MODO DE FUNCIONAMIENTO.
MODO DE
ONEXIÓN AUTOMÁTICA. FUNCIONAMIENTO
- Para habilitar la REConexion automática, la tapa roja transparente tiene que cerrarse
deslizandose suavemente sobre el interruptor diferencial. El equipo esta en modo AUTO, led
verde esta en ON (parpadeando en caso de estar en modo de aislamiento) y por tanto después
de una desconexión por disparo diferencial el equipo empieza la reconexion automática.
- Para deshabilitar esta funcion, la tapa roja transparente debe estar abierta. El equipo esta en
modo MANUAL, led verde esta en OFF y por tanto no reconecta automaticamente.
-
Tension Nominal
..................... 230 / 400 Vac 50-60 Hz
Intensidad Nominal ..................... 40 A c.a. / 63 A c.a.
Sensibilidad, I n ........................ 30 mA
Resistencia a ondas de choque ..... 250 A 8/20 s / 200 A 0,5 s
Resistencia al cortocircuito .............. 6.000 A segun VDE 0664
Intensidad Nominal de apertura y cierre ....................... 500 A
Clase ............................................................................ A (IEC 1008.1)
Numero de polos .......................................................... 2 / 4
Tensión de test ............................................................ 2 polos, entre 140 y 230 Vac
4 polos, entre 190 y 400 Vac
Bornes de conexion ....................................................
35 mm2
Grado de proteccion .................................................... IP40 (DIN 40050)
Temperatura de stock ................................................... - 55 C a 55 C
Temperatura servicio ..................................................... - 25 C a 55 C
Normativa ...................................................................... IEC 61008.1
Caja color ...................................................................... RAL 7035
-
(mm)
REC
CARACTERISTICAS INTERRUPTOR DIFERENCIAL
DIMENSIONES
D
m
m
Con el interruptor de modo reconexión
el equipo esta en modo de Secuencia
.
Despues de una desconexión por disparo por diferencial se intenta realizar hasta un máximo de
6 reconexiones con una temporización entre rearmes de 10, 20, 30, 60, 120 y 600 segundos. En
esta situación el led rojo parpadea lentamente indicando temporización entre reconexiones.
Llegando a la no reconexion permanente si se agota el numero de rearmes y el problema
persiste. En tal caso el led rojo queda en ON fijamente. El tiempo de reset del numero de
reconexiones es de 300 segundos.
- Con el interruptor hacia
se esta en modo
, el equipo realiza la misma
operación de temporización de rearmes solo que antes de reconectar realiza un test de control
de aislamiento, 5 segundos de supervisión continua, durante el cual el led rojo parpadea
rápidamente. Si el test es negativo el equipo reconecta automaticamente. Si el test es positivo,
el equipo no reconecta y temporiza el siguiente tiempo. Una vez agotada la secuencia el equipo
se bloquea, en estado de no reconexión permanente, quedando el led rojo fijamente en ON.
abajo
Tiempo
arriba
supervisión de fuga
Código
code
Descripción
Description
Polos
Poles
Intensidad Nominal (A)
Nominal Current
P26611
REC2C 2P-40-30M
2
40
30
Sensibilidad, I N (mA)
D
Sensibility
OPERATION MODE .
SELF-RECLOSING MODE . OPERATION
- To enable the automatic reclosing, the red transparent lid has to be closed slipping softly
on RCCB. The equipment is in automatic mode, green led is in ON (blinking in the case
that it’selected isolation control mode) and therefore after one disconnection by earth
leakage trip the equipment begans the automatic reclo-sing.
- To disable this function, the red transparent lid should be open.The equipment is in manual
mode, green led is in OFF and therefore it doesn’t reclose automatically. In this
operation mode we can check RCCB by means of push-button TEST.
- With the reclosing
the equipment is in
mode.
After one disconnection by earth leakage trip, it tries to realize up to a maximum of 6
reconnections with a time between reclosures of 10, 20, 30, 60, 120 y 600 seconds.In
this situation the red led is blinking slowly indicating the timing between reclousures.
Reaching to not reclose permanent if the number of reclousures have been finished
and the problem continues. In this case the red LED remains in ON fixedly.The
time to reset the number of reclousures is 300 seconds.
- Witch the reclosing
, it realizes a test of earth leakage. If the test is
negative, the equipment will reclose automatically.If the test is positive,the equipment
will not reclose and the time will pass 5 seconds of supervision during witch the red
led blinks fast. When this period is finished the equipment locks, leaving the
equipment a state of non-permanent reconnection, witch the red led in ON fixely.
Auxiliary power supply
..................... 230 / 400 Vac 50-60 Hz
Rated ....................................... 40 A c.a. / 63 A c.a.
Sensitivity, I n ........................ 30 mA
Resistance to shock waves ..... 250 A 8/20 s / 200 A 0,5 s
Rated cut off power .................. 6.000 A segun VDE 0664
Rated opening and closing ....................... 500 A
Class ............................................................................ A (IEC 1008.1)
Number of poles ........................................................... 2 / 4
Tension Test ............................................................... 2 polos, entre 140 y 230 Vac
4 polos, entre 190 y 400 Vac
Bornes Connection .................................................... 35 mm2
Protection grade ........................................................... IP40 (DIN 40050)
Temperature Stock .................................................... - 55 C a 55 C
Temperature service ..................................................... - 25 C a 55 C
Standards ..................................................................... IEC 61008.1
Color Box ...................................................................... RAL 7035
switch down
time sequence
switch upwards
FEATURES OF RCCB
D
m
m
Interruptor Diferencial
2/4 polos
Frontal deslizante
para bloqueo / reset equipo
Front slider for blocking and
reset equipment
LED-s indicando
estado del equipo:
. Estado ON
. Estado disparado
. Estado reconexion
Conmutador frontal para
seleccionar modo
reconexion.
GENERAL DESCRIPTION
DESCRIPTION OF LED´s AND SWITCH
- RCCB class A (IEC 1008.1)
- It has self-reclosing system.
· Isolation Control Mode
· Time Sequence Mode
- Mounting in DIN rail 46277 (EN 50022)
- Green LED.
· MANUAL reclosing (OFF)
· AUTOMATIC reclosing (ON)
- Blinking fast, it’s indicating the reclosing sequence.
- Reclosing Mode.
· Supervision of earth leakage. Switch upwards M
·Time sequence. Switch down. T
- Red LED.
· OFF, RCCB is not tripped.
· ON, RCCB is tripped.
- Blinking slow, it’s counting the reclosing sequence.
- Blinking fast,the reclosing sequence has been finished,
but earth leakage is being detected, avoiding the
reconnection while earth leakage remains.
· Fixed, there is a earth leakage trip and it is in not self-reclosing
situation.
LEDs indicating
the status of equipment:
. AUTO / ON
. Trip / Reclosing
RCCB 2 or 4 poles
Front switch for configure
self reclosing type
-
P26614
REC2C 2P-63-30M
2
63
30
P26612
REC2C 4P-40-30M
4
40
30
P26
615 REC2C 4P-63-30M
4
63
30
ATENCION: Este sistema de reconexion solo es valido para las protecciones de 2 polos.