Edmk manual, Nd ns, Communications description – CIRCUTOR EDMk Series User Manual
Page 2: Display / leds, Connections 9. technical characteristics, Technical assistance service, Type mc3
6.5. Communications description
One or more EDMk meters can be connected to a computer or PLC. As well as the usual operation of each piece of
equipment, this system may centralize data at one single point. The EDMk has an RS-485 series communications
output. If more than one analyzer is connected to one RS-485 communication bus, it is necessary to assign to each a
peripheral address (from 01 to 255) so that the remote computer or PLC sends data on different measured or calculated
recordings to those addresses. The RS-485 connection is made with woven mesh shielded communications cables,
with a minimum of three wires and with a maximum distance between remote computer and the last analyzer of 1.200
metres. This RS-485 series bus can connect up to a maximum of 32 devices.The EDMk meter communicates using the
MODBUS RTU© protocol (Pulling Question / Answer).
7. DISPLAY / LEDS
-
L1
-,
L2
- and
L3
- shows that the device has measured voltage in each phase. If one of these does not exist, the corresponding identifi cation number does not
appear. The symbols appearing behind each phase (L) indicate the direction of the current in the current transformers, showing if the point of measurement
is consuming or generating energy (
L1
,
L2
and
L3
fl ashing, informs of possible errors of connection of current transformers).
-
T1
,
T2
y
T3
(identifi cation only available on the EDM3k; shows the tariff selected for that time, independently from the tariff displayed on the upper
section.
- The
symbol indicates that load is inductive. The
symbol indicates a capacitive load.
- The
symbol shows that the meter is the fi rst and fourth quadrant (consumption). The
symbol indicates that the meter is in the second and third
quadrant (generation).
8. CONNECTIONS
9. TECHNICAL CHARACTERISTICS
EDMk-ITF-RS485-C2
Intelligent converter
Ethernet converter
M31751
M54020
M54031 / M54032
BORNES RS-485
BORNES RS-485
RS-485 / RS-232
A (+)
1 (A(
A
B (-)
2 (B)
B
S (GND)
5 (GND)
S
10. TECHNICAL ASSISTANCE SERVICE
In the event of any equipment failure or any operational queries please contact the technical service of CIRCUTOR, SA.
CIRCUTOR, SA. – After sales service.
Vial Sant Jordi s/n
08232 Viladecavalls, Barcelona
EDMk Manual
M98204801-03-11A
Tel.: (+34) 93 745 29 00
Fax: (+34) 93 745 29 14
e-mail: [email protected]
3 or 4 wires (low voltage)
3 wires (2 VT y 2 CT)
MC1-20 (example 200A)
MC1-30 (example 500 A)
L1
L2
L3
min
max Pd
N
max
clear
COMM
CPU
CVM-MINI
reset
N
N
reset energy
N
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
b
B
a
A
b
B
a
A
V
L1
V
L2
V
L3
S2
P2
S1
P1
S2
P2
S1
P1
POWER SUPPLY
TIPO C.A.
TIPO C.C. & C.A.
Single phase
230 V a.c.
85..265 Va.c./ 95...300 Vd.c
Voltage tolerance
-15 %... +10 %
Frequency
45...65 Hz
0...65 Hz
Maximum burden
5 V·A
Operating temperature
-20 ºC...+60 ºC
-20 ºC...+60 ºC
Humedity (without condensation)
5 %...95 %
Maximum altitude
2.000 m
MECHANICAL FEATURES
Casing material
Self extinguishing VO plastic
Protection assembled device (front)
IP 51
Protection non assembled device
IP 31
Supply and voltage measure wires
Minimum section 1 mm²
Secondary current transformers wires
Minimum section 2,5 mm²
Dimensions (mm)
85 x 52 x 70 (3 steps)
CLASS
Acuracy class in active energy
Class 1 - EN62053-21
Accuracy class in reactive energy
Class 2 - EN62053-23
STANDARDS
EN62052-11, EN62053-21, EN62053-23, EN61010-1
MEASUREMENT CIRCUIT
Rated voltage
300 V a.c. f-N / 500 V a.c. f-f
Frequency
45...65 Hz
Rated current
.../5 or .../1
Permanent overload
1,2 In
Voltage circuit burden per phase
0,3 V·A
Current circuit burden per phase
0,3 V·A at 5 A. ó 0,06 V·A at 1 A
PULSE OUTPUT TRANSISTOR FEATURES
Opto-insulated transistor (open collector)
NPN
Maximum operating voltage
24 V c.c.
Maximum operating current
50 mA
Maximum frequency
5 imp / s
Pulse length
50 ms
TRANSISTOR OUTPUTS CONNECTIONS
Output 1
Terminal 9 - 8
Output 2
Terminal 7 - 8
MAXIMUM COUNTER VALUE
9999999 kW
SAFETY
Category III EN61010-1. Class II double
insulation against electric shock.
TYPE MC3
The EDMk energy meter display is divided into two sections: the fi rst of these (on the upper section) displays the value of the energy meters (Active energy and Inductive
reactive energy or Capacitive). The second shows the measurement, in real time, being taken by the meter at that time.
CPU
CPU led indicates that the device is working right fl ashing in one second intervals.
COMM
COMM led fl ashes quickly in varible intervals when the device is receiving or sending information throught is RS-485 port.
Set A
NS
Display
ND
NS
Setup
Clear
NC
1 2 3 4 5 6 7 8 9
L1
L2
L3
N
1P1
2P1
3P1
1P2
2P2
3P2
COM
2S1
L1
L2
L3
N
1P1
2P1
3P1
1P2
2P2
3P2
1S1
3S1
Set A
NS
Display
ND
NS
Setup
Clear
NC
1
2
3
4
5
6
7
8
9
L1
L2
L3
L1
L2
L3
1S11S22S12S2
1S11S22S12S2
MC1-20
MC1-20
1S11S22S12S2
MC1-20
Set A
NS
Display
ND
NS
Setup
Clear
NC
1
2
3
4
5
6
7
8
9
L1
L2
L3
L1
L2
L3
1S11S22S12S2
1S11S22S12S2
MC1-30
MC1-30
1S11S22S12S2
MC1-30