Table 6

out

Parameter

symbol

Description

Range of changes

P_An

Input quantity, on which the
analog output has to react.

InP1 – main input (indicated

value).
InP2 – input of the auxillary

counter.

AnL

Lower threshold of the analog
output. One must give the value,
on which we want to obtain the
minimal value of signal on the
analog output.

-19999...99999

AnH

Upper threshold of the analog
output. give the value on which
we want to obtain the maximal
value of signal on the analog
output (10 V or 20 mA).

-19999...99999

tyPA

Type of analog output

0_10U – voltage 0...10 V
0_20A – current 0...20 mA
4_20A – current 4...20 mA

bAud

Baud rate of the RS-485 interface

4.8 – 4800 bit/s
9.6 – 9600 bit/s
19.2 – 19200 bit/s
38.4 – 38400 bit/s
57.6 – 57600 bit/s
115.2 – 115200 bit/s

prot

Type of transmission frame of the
RS-485 interface.

r8n2
r8E1
r8o1
r8n1

Addr

Address in the MODBUS net-
work. The write of the value 0
switches the interface off.

0...247