beautypg.com

Controls cont – WaterFurnace Envision Low Sill User Manual

Page 28

background image

28

ENVISION LOW SILL CONSOLE INSTALLATION MANUAL

Controls cont.

Mode

Inputs

Blower

Comp

RV

Htg

Y

ON

ON

OFF

Clg

Y,O

ON

ON

ON

Blower

G

ON

OFF

OFF

Switch

OFF

ON

SW1 - 1

Test - Selected timings sped up to facilitate troubleshooting

Normal - Standard timings

SW1 - 2

Loop - Closed loop freeze detection setting (15°F)

Well - Open loop freeze detection setting (30°F)

SW1 - 3

Commercial - Enables NS features when TA32U02 thermostat is used

Normal - Standard thermostat operation

SW1 - 4

IO Display* - Enables Input/Output display on external LED board

Normal* - Unit status display

SW1 - 5

Configures board for 2-speed compressor without blower

Configures board for 2-speed compressor with blower

Logic Board DIP Switch Settings

Blower off delay

30 seconds

Compressor on delay

10 seconds

Short cycle delay

5 minutes

Minimum compressor on time

2 minutes (except for fault condition)

High pressure fault recognition delay

Less than 1 second

Low pressure fault recognition delay

30 seconds

Freeze detection fault recognition delay

30 seconds

Condensate overflow fault recognition delay

30 seconds

Low pressure fault bypass delay

2 minutes

Freeze detection fault bypass delay

2 minutes

Power on delay

5 minutes

Normal Control Timing

Operational Logic

Blower off delay

5 seconds

Compressor on delay

2 seconds

Short cycle delay

15 seconds

Minimum compressor on time

5 seconds (except for fault condition)

High pressure fault recognition delay

Less than 1 second

Low pressure fault recognition delay

30 seconds

Freeze detection fault recognition delay

30 seconds

Condensate overflow fault recognition delay

30 seconds

Low pressure fault bypass delay

0 seconds

Freeze detection fault bypass delay

0 seconds

Power on delay

15 seconds

Fault off time

5 minutes

Test Control Timing

LED

Current Fault Status

SW1 - #4 On, SW2 On

Inputs

SW1 - #4 Off, SW2 Off

Outputs

SW1 - #4 Off, SW2 On

Drain

Drain pan overflow

Y

Compressor

Water Flow

FD thermistor (loop <15°F, well <30°F)

G

Blower

High Press

High pressure >600 psi

O

O

Low Press

Low pressure <40 psi

ES

ES

Air Flow

Not used

Not Used

Not Used

Status

Not used

Not Used

Not Used

DHW Limit

Not used

Not used

Not used

HWD

SW2 in the On position

Off position

On position

Diagnostic Modes

Control Tables for Optional Versatec Microprocessor