Electrical data, Blower performance data, Blower performance data electrical data – WaterFurnace Envision Low Sill User Manual
Page 18
18
ENVISION LOW SILL CONSOLE INSTALLATION MANUAL
Blower Performance Data
Electrical Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
09
115/60/1
104/127
12.5
8.0
50.0
1.5
9.5
11.5
15
208-230/60/1
187/253
6.4
4.1
21.0
0.6
4.7
5.7
10/15
265/60/1
238/292
6.7
4.3
22.0
0.6
4.9
6.0
10/15
12
115/60/1
104/127
14.8
9.5
50.0
1.5
11.0
13.4
20
208-230/60/1
187/253
7.7
4.9
25.0
0.6
5.5
6.7
10/15
265/60/1
238/292
7.0
4.5
22.0
0.6
5.1
6.2
10/15
15
208-230/60/1
187/253
9.2
5.9
29.0
2.6
8.5
10.0
15
265/60/1
238/292
7.8
5.0
28.0
2.5
7.5
8.7
10/15
18
208-230/60/1
187/253
10.4
6.7
33.5
2.6
9.3
11.0
15
265/60/1
238/292
8.7
5.6
28.0
2.5
8.1
9.5
15
HACR circuit breaker in USA only
6/10/13
Model
CFM
Low Speed
High Speed
09
260
300
12
300
340
15
375
450
18
450
600
Air fl ow values are with dry coil and standard fi lter.
For wet coil performance, fi rst calculate the face velocity of the air coil
(face velocity (fpm) = airfl ow (cfm) / face area (sq ft))