ENVISION LOW SILL CONSOLE INSTALLATION MANUAL

Unit Mounted Control

The user selects either “Heat/Cool” or “Fan Only” on the

mode switch, then either “High” or “Low” at the blower

speed switch. The temperature can be controlled by

rotating the thermostat control knob.

The “Fan Only” setting provides constant blower operation.

In the “Heat” mode, a call for heat by the thermostat

closes the compressor contactor contacts, energizing the

compressor, which will run until the thermostat is satisfied.

In the “Cool” mode, a call for cooling by the

thermostat energizes the reversing valve and closes

the compressor contactor contacts, energizing the

compressor, which will run until the thermostat is satisfied.

If either the low or high pressure safety switches are

opened, the compressor and reversing valve are disabled

by the lockout relay. Unit operation will resume only after

the voltage to the unit is interrupted or the mode switch is

placed in the “Off” position.

Optional Versatec Microprocessor
Control Features

The Versatec microprocessor board provides control of

the entire unit as well as outputs for status modes, faults

and diagnostics. The control system is a microprocessor-

based control board that is located in the unit control box.

This feature is available for either unit mounted controls

or optional remote wall mounted thermostat. A 9-pin low

voltage terminal strip provides all necessary terminals for

the wall mounted thermostat.

Startup

The unit will not operate until all the inputs and safety

controls are checked for normal operating conditions.

Fault Retry

All faults are retried twice before finally locking the unit

out to prevent nuisance service calls.

Component Sequencing Delays

Components are sequenced and delayed for optimum

unit performance.

Emergency Shutdown

A grounded signal to common or connecting 24 VAC to

the ES terminal places the controller into the emergency

shutdown mode. The compressor and blower operation are

suspended while in the emergency shutdown mode.

Condensate Overflow Protection

The board incorporates an impedance liquid sensor at

the top of the condensate drain pan. Upon a continuous

30-second sensing of the condensate, the cooling

operation of the unit is suspended.

Safety Controls

The microprocessor board receives separate signals from

a high pressure switch for safety, a low pressure switch

to prevent loss of refrigerant charge and a low suction

temperature thermistor for freeze detection. Upon a

continuous 30-second measurement of the fault (immediate

for high pressure), compressor operation is stopped.

Controls cont.