Operating parameters, Operating limits, Single speed models – WaterFurnace Envisio Series Console User Manual
Page 39: Envision console - 50 hz installation manual
39
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Operating Parameters
Single Speed Models
Operating Limits
Operating Limits
Cooling
Heating
(°F)
(°C)
(°F)
(°C)
Air Limits
Min. Ambient Air
45
7.2
45
7.2
Rated Ambient Air
80
26.7
70
21.1
Max. Ambient Air
100
37.8
85
29.4
Min. Entering Air
50
10.0
40
4.4
Rated Entering Air db/wb
80.6/66.2
27/19
68
20.0
Max. Entering Air db/wb
110/83
43/28.3
80
26.7
Water Limits
Min. Entering Water
30
-1.1
20
-6.7
Normal Entering Water
50-110
10-43.3
30-70
-1.1
Max. Entering Water
120
48.9
90
32.2
NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependant upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.
Entering
Water Temp
°C
Water Flow
l/s/kW
Cooling
Suction Pressure
kPa
Discharge
Pressure kPa
Superheat
Subcooling
Water Temp
Rise °C
Air Temp Drop
°C DB
10
0.1
876 - 993
1413 - 1551
3 - 6
6 - 8
10 - 12
10 - 12
2.9
827 - 965
1276 - 1413
4 - 8
3 - 6
4 - 6
10 - 12
21
0.1
958 - 1062
1931 - 2068
4 - 6
4 - 7
10 - 12
10 - 12
2.9
945 - 1048
1724 - 1862
5 - 7
4 - 6
4 - 6
10 - 12
32
0.1
986 - 1089
2482 - 2620
4 - 6
5 - 7
10 - 12
9 - 11
2.9
972 - 1076
2275 - 2413
5 - 7
4 - 7
4 - 6
9 - 11
8/17/10
Entering
Water Temp
°C
Water Flow
l/s/kW
Heating
Suction Pressure
kPa
Discharge
Pressure kPa
Superheat
Subcooling
Water Temp
Drop °C
Air Temp Rise
°C DB
10
0.1
503 - 545
1924 - 2096
4 - 7
1 - 3
4 - 6
10 - 13
2.9
545 - 586
1965 - 2137
4 - 8
1 - 3
2 - 3
11 - 14
21
0.1
710 - 752
2124 - 2296
4 - 7
2 - 4
4 - 6
11 - 14
2.9
758 - 800
2172 - 2344
5 - 7
2 - 4
2 - 4
12 - 16
32
0.1
965 - 1007
2275 - 2517
6 - 8
4 - 6
6 - 8
14 - 18
2.9
1007 - 1055
2344 - 2586
6 - 8
4 - 6
4 - 6
16 - 19
8/17/10
NOTE: Cooling performance based on entering air temperatures of 27°C DB, 19°C WB. Heating performance based on entering air
temperature of 21°C DB.