beautypg.com

Envision controls cont, Fx10 user interface (mui) physical layout – WaterFurnace Envisio Series Console User Manual

Page 35

background image

35

ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL

Envision Controls cont.

FX10 User Interface (MUI) Physical Layout

Power LED

LED 1

LED 4

Escape (ESC)
Button

Return Button

Alarm LED

LED 8

Up Arrow

Right Arrow

Left Arrow

Down Arrow

Alarm LED - Indicates a Lock-Out or a bad Freeze Sensor

Power LED - Shows FX processor is operational

LED 1 - Flashing shows Compressor 1 running

LED 2 - Flashing shows Full Capacity Compressor running

LED 3 - On shows Fan running

LED 4 - On shows Reversing Valve in cool

LED 8 - Flashing shows unit in ‘Test’ Mode

MUI Menu Navigation for Single Compressor - Envision Water-to-Air

Welcome

Info Status Temps Outputs Settings Maint Alarms Alm-History

Water Source

Heat Pump

PROFXENV-XX

_/_/__

Info

Run Mode

Auto

Eff Occup’y

Occ

Y1 Input

OFF

Y2 Input

OFF

G Input

OFF

O Input Heat/Cool

Occ Input

Occ

Temp Occ Inp

OFF

Condensate NML

Emg Input

Run

Lo Press

ON

Hi Press

ON

Rndm Tmr

0

BI-4 Input

OFF

Status

Zone Temp

25.1 ºC

Dis Air Temp

10.6 ºC

Eff Clg Setpt

21.1°C

Eff Htg Setpt

18.9°C

Water Coil

25.4°C

Low WC Limit

-1.1°C

Humidity 56.7

%RH

WarmCool AI

14.6

WarmCoolAdj

0.2

Temps

nvoFanStatus ON

CmpCmd Status

OFF

Cmp Capacity

OFF

Rev Valve

Heat

X1 Output

OFF

X2 Output

OFF

PWMOut 98%

BO5 OFF

BO9 OFF

AO2 Output

0%

Outputs

Settings

Unit of Measure

C

Occ Clg Setpt

23.3 ºC

Occ Htg Setpt

21.1 ºC

Unocc Clg

28.9 ºC

Unocc Htg

15.6 ºC

DeHumSetpt 0%

SensorSelect TAXXJ02