Envision controls cont, Inputs and outputs configuration, Control accessories – WaterFurnace Envisio Series Console User Manual
Page 34: Field selectable options
34
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
MUI Alarm History Reporting
If a fault occurs the fault will be recorded in history for
display on the medium user interface in the History Menu.
Each fault type will be displayed in the history menu with
a number between 0 and 3. A reading of 3+ will mean that
fault has occurred more than three times in the past. The
history menu can be cleared with a power cycle only. Alarm
date and time are not included in the history.
Inputs and Outputs Configuration
Field Selectable Options
Freeze Detection Limit Set Point (BI-5)
The freeze detection limit set point input allows you to
adjust the freeze detection limit set point (AI-5). When the
jumper is installed on BI-5 (Wire #24) the freeze detection
limit set point is factory set for 30°F [-1°C]. When the
jumper on BI-5 (Wire #24) is removed the freeze detection
set point will be 15°F [-9°C].
Accessory Outputs (BO-7 and BO-8)
Accessory Output 1 will be energized 90 seconds prior to
the compressor output being energized. Accessory Output
2 will be energized with the blower output (BO-1). When
the corresponding compressor output is turned off the
accessory output will be deactivated immediately. These
outputs are selectable for normally open or normally closed
operation through the Medium User interface or through the
Building Automation System.
Control Accessories
Zone Sensors
• TAXXJ02 Room Command Module
• TAXXA01 LCD Room Command Module
• A99
Sensor
MUI (LCD User interface) for diagnostics
and commissioning.
• MUIK3 - Panel Mount, Portable
• MUIK4 - Wall Mount
Envision Controls cont.
Input Name
Input
Output Name
Output
Zone Temp 1
AI 1
Fan Enable
BO1
Relative Humidity Input
AI 2
Comp – Low Capacity
BO2
Condensate Level
AI 3
Reversing Valve
BO3
Universal Temp Input
AI 4
Comp – Full Capacity
BO4
Water Coil Low Temperature Limit
AI 5
Network Output/EH Output
BO5
Warm/Cool Adjust and Temp Occ
AI 6
Alarm
BO6
Accessory 1 Output
BO7
Occupied
BI 1
Accessory 2 Output
BO8
Emergency Shutdown
BI 2
Network Controlled Output
B09
Stage 1 Low Pressure
BI 3
Network Viewable Input 1
BI 4
ECM2 Fan
PWM1
Water Coil Low Temp Limit Set Point
BI 5
Network Controlled Output
PWM2
Network Viewable Input 2
BI 6
Thermostat Y1
BI 7
Thermostat Y2
BI 8
Thermostat O
BI 9
Thermostat G
B10
Stage 1 High Pressure
BI11
Compressor Proving
BI12
XP10 Expansion Card
Input Name
Input
Output Name
Output
Unused
AI 1
Unused
BO 1
Unused
AI 2
Unused
BO 2
Unused
AI 3
Unused
BO 3
Unused
AI 4
Unused
BO 4
SINGLE and DUAL STAGE WATER-TO-AIR