Electrical data, Blower performance data, Electrical data blower performance data – WaterFurnace Envisio Series Console User Manual
Page 21: Envision console - 50 hz installation manual, Ecm blowers psc blowers, Psc blowers ecm blowers
21
ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL
Electrical Data
Blower Performance Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
02
220-240/50/1
198/264
6.4
4.1
17.0
2.6
6.7
7.7
10/15
03
220-240/50/1
198/264
7.6
4.9
18.7
2.6
7.5
8.8
10/15
04
220-240/50/1
198/264
9.2
5.9
23.0
2.6
8.5
10.0
15
05
220-240/50/1
198/264
10.5
6.7
24.0
2.6
9.3
11.0
15
HACR circuit breaker in USA only
3/05/14
ECM Blowers
PSC Blowers
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
02
220-240/50/1
198/264
6.4
4.1
17.0
0.50
4.6
5.6
10/15
03
220-240/50/1
198/264
7.6
4.9
18.7
0.50
5.4
6.6
10/15
04
220-240/50/1
198/264
9.2
5.9
23.0
0.69
6.6
8.1
10/15
05
220-240/50/1
198/264
10.5
6.7
24.0
0.69
7.4
9.1
15
HACR circuit breaker in USA only
3/05/14
Model
LPS
Low Speed
High Speed
02
120
140
03
120
140
04
175
200
05
175
200
Factory settings are in Bold
Air fl ow values are with dry coil and standard fi lter.
For wet coil performance fi rst calculate the face velocity of the air
coil (Face Velocity [mps] = Airfl ow [lps] / Face Area [m
2
]). Then for
velocities of 1 mps, reduce the static capability by 7.5 pa, 1.5 mps by 19.9
pa, 2 mps by 29.9 pa and 2.5 mps by 39.8 pa.
PSC Blowers
ECM Blowers
Model
LPS
Low Speed
Medium Speed
High Speed
02
140
150
190
03
140
150
190
04
165
210
280
05
165
210
280
Factory settings are in Bold
Air fl ow values are with dry coil and standard fi lter.
For wet coil performance fi rst calculate the face velocity of the air
coil (Face Velocity [mps] = Airfl ow [lps] / Face Area [m
2
]). Then for
velocities of 1 mps, reduce the static capability by 7.5 pa, 1.5 mps by 19.9
pa, 2 mps by 29.9 pa and 2.5 mps by 39.8 pa.