beautypg.com

Specifications, System assembly, General specifications – Spectrum Controls 1762sc-OF8 User Manual

Page 8

background image

MicroLogix™ Analog Output Module

Publication 0100163-01 Rev. B

Controller

Max 5V

Bus Current

(mA)

Max 24V

Bus Current

(mA)

Max # of OF8

Modules

ML1100 800 700

3

ML1200

(24pt.)

400 350

1

ML1200
(40pt.)

600 500

2

ML1400 1500 1500

6

System Assembly

The expansion I/O module is attached to the controller or another I/O module by

means of a ribbon cable after mounting as shown below.


Use the pull loop on the connector to disconnect

modules.
Do not pull on the ribbon cable.

MicroLogix™ Analog Output Module

17 

Publication 0100163-01 Rev. B

Specifications

 

General Specifications

  

Specification Description

Isolation
Withstand

Channel to Rack

707 VDC for 1 minute (withstand voltage) Optical & magnetic

Output channel to
channel

Return lines are connected together. No isolation between channels.

Power Requirements

Internal rack +5V

30 mA maximum

Internal rack +24V

250 mA maximum at 18.7V, 195mA max at 24V.

Heat Dissipation

4.9W total Max

Maximum number of
modules on the bus

Distance rating of 6. Maximum number of modules by controller type:

Controller

Max 5V

Bus Current

Max 24V

Bus Current

Max # of

Modules

ML1100 800

700

3

ML1200 (24pt.)

400

350

1

ML1200 (40pt.)

600

500

2

ML1400 1500

1500

6

Fusing None

Wire Size

Up to two wires of size #14-#22 AWG (solid) or #16- #22 AWG
(stranded)

Wire Type

To ensure proper operation and high immunity to electrical noise, always
use Belden 8761 (shielded, twisted pair) or equivalent wire for voltage
and current sensors

Dimensions

90 mm (height) x 87 mm (depth) x 40 mm (width)height including
mounting tabs is 110 mm. 3.54 in. (height) x 3.43 in (depth) x 1.58 in
(width)height including mounting tabs is 4.33 in.

Storage Temperature

-40˚C to +85˚C (-40˚F to 185˚F)

Operating Temperature

-20˚C to 60˚C (-4˚F to +140˚F)

Operating Humidity

5% to 95% non-condensing

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. max peak-to-peak

Shock Operating:

30G

Weight, unpackaged

0.185 kg (0.408 lb) (TBD)

Weight, packaged

0.299 kg (0.615 lb) (TBD)

Module Identification

Vendor I.D.

58

Product Type

10

Product Code

21

Certifications

Agency Certification

C-UL listed (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous Environment
Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T6

Radiated and
Conducted Emissions

IEC61000-6-4 FCC Part 15B Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity
(IEC61000-4-2)

4 kV contact, 8 kV air

Radiated Immunity
(IEC61000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation, 900 MHz & 1890
MHz 100% amplitude modulation