Specifications, System assembly, General specifications – Spectrum Controls 1762sc-OF8 User Manual
Page 8

MicroLogix™ Analog Output Module
8
Publication 0100163-01 Rev. B
Controller
Max 5V
Bus Current
(mA)
Max 24V
Bus Current
(mA)
Max # of OF8
Modules
ML1100 800 700
3
ML1200
(24pt.)
400 350
1
ML1200
(40pt.)
600 500
2
ML1400 1500 1500
6
System Assembly
The expansion I/O module is attached to the controller or another I/O module by
means of a ribbon cable after mounting as shown below.
Use the pull loop on the connector to disconnect
modules.
Do not pull on the ribbon cable.
MicroLogix™ Analog Output Module
17
Publication 0100163-01 Rev. B
Specifications
General Specifications
Specification Description
Isolation
Withstand
Channel to Rack
707 VDC for 1 minute (withstand voltage) Optical & magnetic
Output channel to
channel
Return lines are connected together. No isolation between channels.
Power Requirements
Internal rack +5V
30 mA maximum
Internal rack +24V
250 mA maximum at 18.7V, 195mA max at 24V.
Heat Dissipation
4.9W total Max
Maximum number of
modules on the bus
Distance rating of 6. Maximum number of modules by controller type:
Controller
Max 5V
Bus Current
Max 24V
Bus Current
Max # of
Modules
ML1100 800
700
3
ML1200 (24pt.)
400
350
1
ML1200 (40pt.)
600
500
2
ML1400 1500
1500
6
Fusing None
Wire Size
Up to two wires of size #14-#22 AWG (solid) or #16- #22 AWG
(stranded)
Wire Type
To ensure proper operation and high immunity to electrical noise, always
use Belden 8761 (shielded, twisted pair) or equivalent wire for voltage
and current sensors
Dimensions
90 mm (height) x 87 mm (depth) x 40 mm (width)height including
mounting tabs is 110 mm. 3.54 in. (height) x 3.43 in (depth) x 1.58 in
(width)height including mounting tabs is 4.33 in.
Storage Temperature
-40˚C to +85˚C (-40˚F to 185˚F)
Operating Temperature
-20˚C to 60˚C (-4˚F to +140˚F)
Operating Humidity
5% to 95% non-condensing
Vibration
Operating: 10 to 500 Hz, 5G, 0.030 in. max peak-to-peak
Shock Operating:
30G
Weight, unpackaged
0.185 kg (0.408 lb) (TBD)
Weight, packaged
0.299 kg (0.615 lb) (TBD)
Module Identification
Vendor I.D.
58
Product Type
10
Product Code
21
Certifications
Agency Certification
C-UL listed (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous Environment
Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T6
Radiated and
Conducted Emissions
IEC61000-6-4 FCC Part 15B Class A
Electrical /EMC:
The module has passed testing at the following levels:
ESD Immunity
(IEC61000-4-2)
4 kV contact, 8 kV air
Radiated Immunity
(IEC61000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, 900 MHz & 1890
MHz 100% amplitude modulation