When wiring the terminal block, keep the finger-safe cover in place.
1) Refer to section 2.6.1for proper field wiring connections.
2) Route the wire under the terminal pressure plate. You can use the stripped end
of the wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade
lug. See Figure 2-6.
3) Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.904 Nm (8 in-lbs).
4) After wiring is complete, remove the debris shield.
2.6.3 Terminal Door Label
A removable, write-on label is provided with the module. Remove the label from the
door, mark your unique identification of each terminal with permanent ink, and slide the
label back into the door. Your markings (ID tag) will be visible when the module door is
closed. See figure below.
Figure 2-7 (Door Label)
Section 2.7
Module Indicators
The 1762 universal module uses a single green LED to show operational status of the
module. When startup is completed and all internal tests have passed, the LED will
illuminate solid. If the LED remains off, there is an error with the module.