OPTI-UPS IS5000LR User Manual
Page 29
28
Average charging
voltage for each battery
Quick charging mode 14V maximum Trickle charging mode 13.2V ~ 13.9V
adjustable with the remote set-up software.
Protection
Over current protection (SCR control)
Over charging voltage protection (SCR control)
Thermal protection (CPU control) When temperature inside INVERTER AND
UPSis over 45 , charger will stop charging for 2.5 minutes followed by an 1.5
minutes charging. The cycle will be repeated until the temperature is lower
than 44 .
Monitoring
Smart monitoring & warning for failed battery or open-circuit battery.
Auto-detection each time when power on or every 6 days
Communications & Management
Standard Interface port
UPSilon2000 compatible.
RS232 USB port is optional)
Optional Interface part
RJ45 (Surge protection), DB9, USB, SNMP
Control panel
LCD
Audible alarm
Alarm on battery Low battery & Battery over voltage
Alarm on abnormal operation Over load, Short-circuit, & Over heat
EBT (Estimation of
Backup Time) system
Yes
Green mode function
(Auto-shutdown during
blackout)
1% to 14% of full load (adjustable by using the remote set-up software)
The default setting is OFF.
Cooling fan control
Auto on / off, controlled by temperature & operation mode
Environmental and Safety
Operating Temperature
Up to 1500 meters 0 to 40 (32 to 104 )
Transit/storage
Temperature
-15 to 55 (5 to 131 )
Relative Humidity
5 - 95% non condensing
Operating Altitude
0 ~ 3000 meters
Audible noise at 1M from
surface of unit
50 dBA
Isolation
1.5KVac for 1 minute between battery and AC side
Quality control system
ISO 9001