8. SPECIFICATIONS
8.1 IS-LT Long-Run Series (Tower) 1000VA~5000VA
General Features:
Smart backup time estimation for any kind of battery
Adjustable voltage sensitivity, voltage-transfer points, & charging voltage
Generator compatible
Automatic restart of load after INVERTER AND UPS shutdown
Smart AVR function (Two buck / boost modes)
Cold-start capable
Audible alarm
Hot-swappable batteries
Network manageable (SNMP optional)
Full function of LCD display (LED display optional)
Smart battery management
Intelligent double stages of charging control, Wet battery compatible
Thermal control cooling fan
Output
120V Models
230V Models
IS1100LT : 1100VA / 660W
IS2200LT : 2200VA / 1350W
IS3000LT : 3000VA / 1800W
Power Levels crated at
nominal inputs
N / A
IS5000LT : 5000VA / 3200W
Output Voltage
100V/110V/120V Selectable
220V/230V/240V Selectable
Voltage Waveform
Sine wave
Crest Factor
3 1 ; (4.5 1 optional)
Output Frequency
(Synchronized to Mains)
Auto Select for 50/60Hz
47Hz ~ 55Hz for 50Hz nominal; 56Hz ~ 65Hz for 60Hz nominal
Regulation (Nominal)
±5% typical of nominal voltage (optional at ±10% AVR for wide I/P up to ±35%)
Regulation
(Battery mode)
±3% of selected output voltage (adjustable with the remote set-up software)
Transfer time (Typical)
Blackout 4ms; Brownout 4ms; Battery mode to Normal mode 4ms typical
Over current protection Over load alarm level 100% ~ 120%, Over load shutdown level 120% ~ 190%
(Adjustable by using the remote set-up software)
Input