OPTI-UPS IS5000LR User Manual
Page 21
20
5.5 Remote Control
The INVERTER AND UPS can be set for daily shutdown/wake up. This command must be set
through the RS-232 interface. When this function is set, the timer inside the INVERTER AND UPS
will begin to run, and the load will be turned off by the shutdown / wake-up schedule. During the
period of turn-off to the next turn-on, the status LED blinks red every 2 seconds. For LCD version,
the time period to next turn-on will be shown on LCD panel by hour (Ref. item 5.2 of LCD
description).
5.5.1 DIP Switch Settings (Available for Tower long run model, IS5000LT, only)
DIP switch setting
DIP 1
DIP 2
230V System
Down Up
200V
Up Up 220V
Up Down
230V
Down Down 240V
DIP setting is valid only when the DIP3=Down.
To apply the other setting on LCD display,
Please refer to 4.11.
DIP 3 for Setting selection UP=invalid for DIP setting / Down=valid for DIP setting
DIP 4 for Green Mode setting UP=Enable / Down = Disable
DIP Switch Settings (for special design of IS5000LT)
DIP 1
DIP 2
Charging
current
Up Up 25%
Down Up 50%
Up Down 75%
Down Down 100%
NOTE of Charging current control
The setting of DIP 1 & 2 is valid only when the DIP3 =
Down.
DIP 3 = Down, UPS mode DIP 3 = Up, Inverter first.
DIP 4 for Green Mode setting UP = Enabled / Down = Disabled
P.S.: The setting active only after the inverter is re-started
5.6 Reset the INVERTER AND UPS
If any abnormal condition occurs, and the item 4.1 ~ 4.7 can not be executed, please unplug the
line cord and push the button for at least 15 sec., which will reset the INVERTER AND UPS.