27
Regulation (Nominal)
±5% typical of nominal voltage (optional at ±8% AVR for wide I/P up to ±35%)
Regulation
(Battery mode)
±3% of selected output voltage (adjustable with the remote set-up software)
Transfer time (Typical)
Blackout 3ms; Brownout 1ms; Battery mode to Normal mode 1ms typical
Over current protection Over load alarm level 100% ~ 120%; Over load shutdown level 120% ~ 190%
(Adjustable by using the remote set-up software)
Input
120V Models
230V Models
Nominal Voltage
100V/110V/120V Selectable
220V/230V/240V Selectable
Input Frequency
47Hz ~ 65Hz, 50/60Hz auto-sensing
Efficiency
97% (Normal mode)
Noise Filtering
Full time EMI/RFI filtering
Over current protection
By re-settable over current protector
Voltage Range
-20% ~ +22% for selected nominal voltage.
-29% ~ +33% adjustable by using the remote set-up software
AVR Range
(2 Bucks, 2 Boosts)
Enhanced Buck: +15% of selected nominal voltage
Buck mode: +5% of selected nominal voltage
Boost mode: -5% of selected nominal voltage
Enhanced Boost: -12.5% of selected nominal voltage
Surge Protection
IS2000LR / IS2700LR : 440 Joules
IS4000LR / IS5000LR : 660 Joules
Battery
Battery type
Lead-Acid 25Ah
250Ah
Voltage
IS2000LR / IS2700LR : 48Vdc (24Vdc optional)
IS4000LR : 48Vdc (72Vdc optional)
IS5000LR : 48Vdc
Typical backup time
No Limit
Charging method
Smart pulse charging with two charging modes.
Quick charging when battery is not fully charged, trickle charging when battery
is 90% fully charged.
Average charging
current
11A for IS2000LR / IS2700LR / IS4000LR
20A for IS5000LR(48Vdc)
20A Optional for IS2000LR / IS2700LR / IS4000LR(Below 48Vdc)
P.S. At normal line and normal temperature (Average)