Labconco Snuffer Fire Extinguishers 1115004 User Manual
Labconco Accessories for air
![background image](/manuals/738763/1/background.png)
Labconco Instruction Sheet 1115700, Rev J, ECO C066 1 of 5
LABCONCO CORPORATION 8811 Prospect Ave, Kansas City, MO 64132
(816) 333-8811, Fax (816) 363-0130, (800) 821-5525
Snuffer – Model 1115000, 1115002, 1115003, 1115004
Internal Hood Depths of
30", 36", & 48"
1. On hoods 4 Ft, 5 Ft and 6 Ft in width, locate the unit at the centerline of the hood per
Fig. 1. Hoods 8 Ft and greater require additional units and should be mounted equal
distance in the hood behind the light assembly shown in Fig. 1. NOTE: Protruding
discharge nozzle should have an unobstructed discharge at the desired protection zone
inside the fume hood.
2. Drill holes per detail “A” of Fig. 1.
Figure 1
3. Mount pedestal bracket with 1/4" stainless steel bolts enclosed. Extinguisher nozzle
should be centered over 1-3/4" diameter hole.
4. Attach extinguisher fusible link tip to unit by threading into gauge nozzle. NOTE:
Unit will not be operational until this tip is re-attached. Use care so as not to damage
link or screw threads.
5. Check extinguisher gauge for charge. Indicator should be in “Green” range.