CAUTION!

11

According to current knowledge, we recommend
cleaning with a 5% phosphoric acid solution or, in
the case that cleaning needs to be performed more
frequently, with a 5% formic acid solution.

In either case, the cleaning fluid should be at room
temperature. It is recommended that the heat
exchanger be cleaned in the direction opposite to
the normal flow direction.

To prevent acidic cleaning agents from entering
the circuit of the heating installation we recom-
mend that the flushing device be fitted directly to
the supply and return lines of the condenser. To
prevent any damage caused by cleaning agent
residues that may be present in the system it is
important that the system be thoroughly flushed
using appropriate neutralising agents.

The acids must be used with great care, all rele-
v a n t r e g u l a t i o n s o f t h e e m p l o y e r s ' l i a b i l i t y
insurance associations must be adhered to.

If in doubt, contact the manufacturer of the chemicals!

Caution - Heating Technicians !

Depending on the filling water quality and

quantity, in particular in the case of mixed

installations and plastic pipes, mineral deposits

(rust sludge, lime) may form, impairing the pro-

per functioning of the heating installation. A

reason for this is the water hardness and

oxygen dissolved in the filling waters as well

as additional oxygen from the air, which may

penetrate via valves, fittings and plastic pipes

(oxygen diffusion). As a preventive measure it

is recommended that a physical water conditio-

ner such as ELYSATOR be used.

9.3 Cleaning of Heat Source Side

The supplied strainer is to be install-

ed in the heat source inlet of the heat pump in

order to protect the evaporator against conta-

mination.

The filter screen of the strainer should be cleaned

one day after commissioning, thereafter every week.

If no more contamination can be noticed any more,

the strainer filter can be removed in order to reduce

pressure losses.

MALFUNCTIONS/
TROUBLESHOOTING

This heat pump is a quality product and is designed

for trouble-free operation. In the event that a

malfunction occurs nevertheless, you will be able to

correct the problem yourself in most of the cases.

Simply consult the Malfunctions and Trouble-

shooting table contained in the operating manual of

the heat pump controller.

Additional malfunctions can be interrogated at the

heat pump controller.

If you cannot correct the malfunction yourself, please

contact the after-sales service agent in charge (see

Warranty Certificate).

All work on the heat pump may only

be performed by an authorised and qualified

after-sales service.

DECOMMISSIONING

11.1 Shutdown in Summer

Shutting down the heating system in summer is

effected by switching the heat pump controller to the

"Summer" operating mode.

11.2 End-of-Life Decommissioning/

Disposal

Before removing the heat pump, disconnect the

machine from the power source and close all valves.

Environment-relevant requirements regarding the

recovery, recycling and disposal of service fuels and

components in accordance with all relevant

standards must be adhered to. Particular attention

must hereby be paid to the proper disposal of

refrigerants and refrigeration oils.

CAUTION!

CAUTION!

CARE/CLEANING

MALFUNCTIONS/TROUBLESHOOTING

DECOMMISSIONING