READ IMMEDIATELY

1.1 Important Information

The heat pump is not secured to the

wooden pallet.

The heat pump must not be tilted

more than max. 45° (in either direction).

Do not lift unit by the holes in the

panel assemblies!

In the case of large-capacity heating

circuits, the installed expansion vessel (24

litres, 1.0 bar admission pressure) must be

supplemented by an additional vessel.

The brine solution must contain at

least 25 % of an antifreeze and corrosion

protection agent on a monoethylene glycol or

propylene glycol basis.

On connecting the electrical load

lines, the clockwise phase sequence must be

observed (in the case of an incorrect phase

sequence the heat pump will deliver no output

and generate a lot of noise).

Commissioning of the heat pump

must be performed in accordance with the

installation and operating manual of the heat

pump controller.

1

PLEASE READ IMMEDIATELY

CAUTION!

CAUTION!

CAUTION!

CAUTION!

CAUTION!

CAUTION!

CAUTION!

CAUTION!

Caution - Heating Contractors !

Depending on the filling water quality and

quantity, in particular in the case of mixed

installations and plastic pipes, mineral deposits

(rust sludge, lime) may form, impairing the pro-

per functioning of the heating installation. A

reason for this is the water hardness and

oxygen dissolved in the filling water as well as

additional oxygen from the air, which may

penetrate via valves, fittings and plastic pipes

(oxygen diffusion). As a preventive measure it

is recommended that a physical water conditio-

ner such as ELYSATOR be used.

CAUTION!

1.2 Legal Provisions and Directives

This heat pump conforms to all relevant DIN/VDE

regulations and EU directives. For details refer to

the EC Declaration of Conformity in the appendix.

The electrical connection of the heat pump must be

performed according to and conforming with all re-

levant VDE, EN and IEC standards. Beyond that, the

connection requirements of the local utility compa-

nies have to be observed.

The heat pump is to be connected to the heat source

and heat distribution systems in accordance with all

applicable provisions.

1.3 Energy-Efficient Use of the Heat

Pump

By operating this heat pump you contribute to the

protection of our environment. A prerequisite for an

efficient operation is the proper design and sizing of

the heating system and the heat source system. In

particular, it is important to keep water flow

temperatures as low as possible. All energy

consumers connected should therefore be suitable

for low flow temperatures. A 1 K higher heating water

temperature corresponds to an increase in power

consumption of approx. 2.5 %. Underfloor heating

systems with flow temperatures between 30 °C and

40 °C are optimally suited for energy-efficient

operation.

The supplied strainer is to be fitted

in the heat source inlet of the heat pump

in order to protect the evaporator against

contamination.

Any work on the heat pump may

only be performed by authorised and qualified

customer service agents.

CAUTION!