beautypg.com

Caution, Commissioning, Care/cleaning – Dimplex S1 7KS User Manual

Page 8: 1 general, 2 preparatory steps, 3 commissioning procedure, 1 care, 2 cleaning of heating side

background image

8

9

COMMISSIONING
CARE/CLEANING

COMMISSIONING

8.1 General

To ensure proper commissioning it should be

carried out by an after-sales service authorised by

the manufacturer. Only then can an extended

warranty period of 3 years in total be granted (cf.

Warranty service).

8.2 Preparatory Steps

Prior to commissioning, the following items need to

be checked:

-

All connections of the heat pump must have been

made as described in Chapter 7.

-

The heat source system and the heating circuit

must be filled and tested.

-

Strainer and vent must be fitted in the brine inlet

of the heat pump.

-

All valves that could impair the proper water flow

must be open in the brine and heating circuits.

-

The heat pump controller must be adapted to the

heating installation in accordance with the

instructions contained in its operating manual.

-

Proper condensate drainage must be ensured.

-

Drainage of the liquid emerging from the brine

and heating water overflow valves must be

ensured.

8.3 Commissioning Procedure

The start-up of the heat pump is effected via the heat

pump controller.

Commissioning of the heat pump

must be carried out in accordance with the

installation and operating manual of the heat

pump controller.

The delivery rate of the circulating pump must be

adapted to the heating system.

The setting of the overflow valve must be adapted to

the requirements of the heating system. An incorrect

setting may result in various error symptoms and an

increased electric power consumption. To correctly

set the overflow valve, the following procedure is

recommended:

8

Close all of the heating circuits that may also be
closed during operation (depending on the type
of heat pump usage) so that the least favourable
operating state - with respect to the water flow
rate - is achieved. Normally, these are the heating
circuits of the rooms located on the south and
west sides of buildings. At least one heating circuit
must remain open (e.g. bathroom).

The overflow valve is to be opened to such an
extent that based on the current heat source tem-
perature the maximum temperature difference
between heating supply and return flow tem-
perature is obtained, as indicated in the table
below. The temperature difference should be
m e a s u r e d a s c l o s e l y t o t h e h e a t p u m p a s
possible. In mono-energetic systems, the electric
heating element is to be deactivated.

Any malfunctions occurring during operation are

indicated on the display of the heat pump controller

and can be corrected as described in the operating

manual of the heat pump controller.

CARE/CLEANING

9.1 Care

The heat pump is designed for maintenance-free

operation. To prevent operating malfunctions caused

by dirt deposits in the heat exchangers, care must be

taken that no contamination whatsoever can enter the

heat source and heating systems. In the event that

operating malfunctions due to contamination occur

nevertheless, the system should be cleaned as

described below.

9.2 Cleaning of Heating Side

The ingress of oxygen into the heating water circuit

may result in the formation of oxidation products (rust).

It is therefore important - in particular with respect to

the piping of the underfloor heating systems - that

the installation is executed in a diffusion-proof manner.

Also residues of lubricating and sealing agents may

contaminate the heating water.

In the case of severe contamination leading to a

reduction in the performance of the condenser in the

heat pump, the system must be cleaned by a heating

technician.

CAUTION!

Heat source temperature

from

to

max. difference between heating

supply and return temperature

-5 °C

0 °C

10 K

1 °C

5 °C

11 K

6 °C

9 °C

12 K

10 °C

14 °C

13 K

15 °C

20 °C

14 K

21 °C

25 °C

15 K