CAUTION!

MOUNTING

pump installations where a power failure cannot

readily be detected (e.g. holiday houses), the heating

circuit must contain a suitable antifreeze product.

The integrated expansion vessel has a capacity of

24 litres.This capacity is appropriate for buildings

with a heated living space floor area of up to 200 m

2

.

The planner of the heating system should verify that

the capacity of the expansion vessel is adequate. An

additional expansion vessel may have to be

installed, if required (as per DIN 4751 Part 1). Charts

in manufacturer catalogues facilitate the proper

selection of the proper size according to the amount

of water in the system.

With large-capacity heating circuits,

the installed expansion vessel (24 litres, 1.0 bar

admission pressure) must be supplemented by

an additional vessel.

7.3 Connection on Heat Source Side

The following procedure must be observed when
making the connection:

Connect the brine line to the flow and return pipe
of the heat pump. The supplied strainer and vent

must be field-installed in the brine inlet of the heat

pump.

The powerful vent must be installed at the highest

point of the heat source system

The hydraulic block schematic must be taken into

account when so doing.

The brine liquid must be produced prior to charging

the system. The brine concentration must be at least

25 %. Freeze protection down to -14 °C can thus be

ensured.

Only antifreeze agents on a monoethylene glycol or

propylene glycol basis are to be used.

The heat source system has to be vented and leak-

tested.

The brine solution must contain at

least 25 % of an antifreeze and corrosion protection

agent on a monoethylene glycol or propylene glycol

basis.

7.4

Electrical Connection

The following electrical connections must be

established on the heat pump.

-

Connection of the load wire to the control panel

of the heat pump.

-

Connection of the control voltage wire to the

control panel of the heat pump.

All electrical components required for the operation

of the heat pump are located on the control panel..

For detailed instructions concerning the connection

of external components and the operation of the heat

pump controller refer to the heat pump terminal dia-

gram and the operating manual of the controller.

Connection of the load wire to the control panel via

terminals X1: L1/L2/L3/PE.

An all-pole disconnecting device with a contact gap

of at least 3 mm (e.g. utility company disable contac-

tor or power contactor) as well as a 3-pole circuit

breaker with simultaneous tripping of all external

conductors must be provided . The required cross-

sectional area of the conductor is to be selected

according to the power consumption of the heat

pump, the technical connection requirements of the

relevant utility company and all applicable regula-

tions. Power consumption data of the heat pump is

provided in the product literature and on the

nameplate. The terminals are designed for a max.

conductor cross-section of 10 mm˝.

The clockwise phase sequence

must be observed when connecting the electric

load lines (in the case of an incorrect phase

sequence the heat pump will deliver no output

and generate a lot of noise).

Connection of the control voltage wire is effected via

terminals X1: L/N/PE.

If a more powerful brine pump is required than the

one integrated, a motor contactor and an appropriate

motor protecting switch need to be installed. The

contactor must be connected to the terminals of the

internal brine pump (controller terminals J12/N03

and X1-N). The power supply of the larger pump

must be provided by the mains supply.

CAUTION!

CAUTION!