3 Water Systems

Diagram 3.2

PUMPED
RETURN

PUMPED
FLOW

6770

3.8 Inhibitor

Attention is drawn to the current issue of BS5449 and BS7593
on the use of inhibitors in central heating systems.

When installing in an existing system take special care to drain
the entire system, including radiators, then thoroughly cleaning
out before installing the boiler whether or not adding an inhibitor.

3.9 Sealed Water Systems

The installation should comply with the appropriate requirements
of the current issue of BS4814, BS5449, BS6759, BS6798 and
BS7074 Part 1 and 2.

3.10 Safety Valve

A safety valve must be fitted to a sealed water system.

It shall be preset, nonadjustable with a lift pressure of 3bar,
incorporating seating of a resilient material, a test device and a
connection for drain.

The drain from the safety valve must be routed clear of any
electrical fittings and positioned so that any discharge can be
seen.

3.11 Expansion Vessel - Sealed Systems Only

A diaphragm type expansion vessel, conforming to the current
issue of BS4814 (see also BS7074 Part 1 and 2) must be
connected at a point close to the inlet side of the circulating
pump, unless laid down differently by the manufacturer.

The expansion vessel volume depends upon the total water
system volume and the initial system design pressure. For any
system an accurate calculation of the vessel size is given in the
current issue of BS7074 Part 1.

Example: For an initial system design pressure of 0.7bar the
minimum total vessel volume required is 0.063xTotal System
volume.

Note. A higher initial design pressure requires a larger volume
expansion vessel.

Guidance on vessel sizing is also given in the current issue of
BS5449 and BS7074 Part 1, for IE refer to the current edition of
I.S.813 "Domestic Gas Installations".

The charge pressure must not be less than the static head of the
system, that is, the height of the highest point of the system
above the expansion vessel.

The water content of the boiler is given in Table 1.

3.12 Pressure Gauge - Sealed Systems Only

A pressure gauge with a set pointer and covering at least the
range of 0 to 4bar (0 to 60lb/in

2

) shall be permanently fitted to

the system in a position where it can be seen when filling the
system.

3.13 Domestic Hot Water Cylinder

SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE.

The domestic hot water cylinder must be of the indirect coil type.
It must be suitable for working at a gauge pressure of 0.35bar
above the safety valve setting.

3.14 Domestic Hot Water System - Unvented

Where a storage system will not have a vent to atmosphere the
installation must comply with Building Regulations and local
Water Company Bye-laws, see also the current issue of BS6700.

If fitting into an existing system the local authority must also be
advised.

22mm
PIPE

22mm
PIPE

22mm
PIPE

22mm
PIPE

FULLY PUMPED CIRCULATION
BYPASS (DIAGRAMMATIC)

22mm FOR COMBINED FEED & VENT TO BE FITTED
IN ACCORDANCE WITH BS5449

3.15 Filling a Sealed Water System

Provision for filling the system at low level must be made.

The installation should comply with the appropriate requirements
of the current issue of BS 5449.

3.16 Water Makeup

Provision must be made for replacing water lost from the
system. A make up vessel mounted above the highest point of
the system and connected through a non-return valve to the
system on the return side of either the hot water cylinder or
heating system.

FULLY PUMPED CIRCULATION
BYPASS (DIAGRAMMATIC)

22mm VENT & 15mm COLD FEED TO BE FITTED
IN ACCORDANCE WITH BS5449