ENMET EX-5150-MOS User Manual

Page 4

background image

EX-5150-MOS

ENMET Corporation

2


2.0 Features of the EX-5150-MOS

See Figure 1 for location of features:

Feature

Description

Display

LCD: Indicates the level of gas detected by sensor

Gain Potentiometer

(POT)

POT 1: Display contrast adjustment
POT 2: Does Not apply to MOS, not used Do not adjust
POT 3: Does Not apply to MOS, not used Do not adjust
POT 4: MOS Heater Voltage, Do not adjust unless advised by

ENMET

Visual Alarms

LED indicators:

Power / Fault Indicator LED, Green / Red
Alarm (3) Indicator LED, Red

Magnetic Switches

M

ENU

: Advances the instrument display through menus (Zero, Span, Exit)

S

ELECT

: Selects the Zero, Span, Exit menu or sets proper calibration values for Zero or Span

Sensor

For sensing gas at

PPM

or LEL levels, see Table 3 for sensor types

Magnetic switches control the instrument maintenance functions. The switch locations are indicated by

M

ENU

and

S

ELECT

. A

magnetic field pulse is applied by momentarily putting the end of the magnet in proximity to the switch and then removing it.
Referred to as tap. Since the magnetic field penetrates the window, the enclosure cover is not removed in order to perform
calibration.

Three alarm points are preprogrammed into the

EX-5150-MOS

sensor/transmitters. At each alarm point, an LED on the front

panel is activated. These internal alarm settings are independent of the 4-20mA output alarm values that can be set at a
controller. An optional relay board is available that will activate 0.5 Amp relay contacts at each alarm point, plus a fault relay.

Figure 1: EX-5150-MOS Features

POT 3

See Note

3 Alarm
Indicators

Power /Fault

Indicator

Display

M

ENU

Magnetic switch

S

ELECT

Magnetic switch

Sensor

Sensor ID is stamped

on the sensor collar:

For example 1

12
13
32

Menu

Select

External View

XX

POT 4

POT 2

See Note

POT 1

Internal PCB View

Note: POT 2 and POT 3 are not

used with EX-5150-MOS
Do Not Adjust