beautypg.com

Cascaded pdus setting – Austin Hughes IPM-01 User Manual

Page 5

background image

www.austin-hughes.com

UM-IPM-01-Q213V2

P.1

PDU cascade port

DIP Switch

1

LINK

OUT

RESET

ON

DIP

1

8

7

6

5

4

3

2

CURRENT

(

A

)

225

Current display

2

Dip switch

3

Reset button

4

Using the dip switch no. 1, 2, 3, 4 & 8 to setup each PDU level as below :

Cascaded PDUs

Dip switch no.

1

2

3

4

8

1st level PDU

On

On

On

On

Off

2nd level PDU

Off

On

On

On

Off

3rd level PDU

On

Off

On

On

Off

4th level PDU

Off

Off

On

On

Off

5th level PDU

On

On

Off

On

Off

6th level PDU

Off

On

Off

On

Off

7th level PDU

On

Off

Off

On

Off

8th level PDU

Off

Off

Off

On

Off

9th level PDU

On

On

On

Off

Off

10th level PDU

Off

On

On

Off

Off

11th level PDU

On

Off

On

Off

Off

12th level PDU

Off

Off

On

Off

Off

13th level PDU

On

On

Off

Off

Off

14th level PDU

Off

On

Off

Off

Off

15th level PDU

On

Off

Off

Off

Off

16th level PDU

Off

Off

Off

Off

Off

Cascaded PDUs setting

For rackmount PDU, on the front panel left , on the rear panel

2

3

4

1

Part I. Seup and Connection
< 1.1 > PDU meter setting & cascade

DIP Switch