Austin Hughes IPM-01 User Manual
Page 36
www.austin-hughes.com
UM-IPM-01-Q213V2
P.32
< 5.2 > Replacement, Removal or addition for PDU & IP dongle
4. How to move out a PDU (without a replacement) ?
Step
1. Prepare an appropriate length Cat. 5/6 cable.
Step
2. Disable alarm email in
Step
3. Use the Cat. 5/6 cable to bridge over the removed PDU to minimize log/data loss.
Step
4. Power off & unplug the device(s) which connected to the PDU.
Step
5. Power off & remove the PDU from connection.
Step
6. Click Disable Monitoring in
Step
7. Enable alarm email in
If the removed PDU NOT in the last level, you MUST reconfi gure and reset the level for the
affected PDU(s) which next to the removed PDU.
Ignore step 1 & 3 if the removed PDU is in the last level.
5. How to add an extra PDU to an existing PDU group ?
Step
1. Prepare a PDU and set the PDU level accordingly.
(Please refer to P.1 for the PDU level setting )
Step
2. Prepare an appropriate length Cat. 5/6 cable.
Step
3. Disable alarm email in
Step
4. Install and connect the new PDU.
Step
5. Power on the new PDU.
Step
6. Click Search in
Step
7. Confi gure the new PDU in
Alarm Amp , Name, Location…
Step
8. Enable alarm email in
If the added PDU NOT in the last level, you MUST reconfi gure and reset the level for the
affected PDU(s) which next to the added PDU.
The company reserves the right to modify product specifi cations without prior notice and assumes no responsibility
for any error which may appear in this publication.
All brand names, logo and registered trademarks are properties of their respective owners.