ADLINK ND-6018 User Manual
Page 102
94
• Calibration
Calibration Procedure for ND-6013 (F/W version A3.05)
1.
Select the correct input range, different input range have different
apply calibration resistance.
2. Apply the correct offset resistance to the analog input module
ND-6013 channel 0, detail resistance value, see table 5-2.
3. Send
“Offset Calibration $(Addr)10” to analog input module
ND-6013 channel 0 .
4. Apply the correct span resistance to the analog input module
ND-6013 channel 0, detail resistance value, see table 5-2.
5. Send
“Span Calibration $(Addr)00” to analog input module
ND-6013 channel 0 .
6. Apply the correct offset resistance to the analog input module
ND-6013 channel 1, detail resistance value, see table 5-2.
7. Send
“Offset Calibration $(Addr)11” to analog input module
ND-6013 channel 1.
8. Apply the correct span resistance to the analog input module
ND-6013 channel 1, detail resistance value, see table 5-2.
9. Send
“Span Calibration $(Addr)01” to analog input module
ND-6013 channel 1.
10. Apply the correct offset resistance to the analog input module
ND-6013 channel 2, detail resistance value, see table 5-2.
11. Send “Offset Calibration $(Addr)12” to analog input module
ND-6013 channel 2.
12. Apply the correct span resistance to the analog input module
ND-6013 channel 2, detail resistance value, see table 5-2.
13. Send “Span Calibration $(Addr)02” to analog input module
ND-6013 channel 2 five times.
14. Repeat procedure 2 to procedure 13 two times.
Calibration Procedure for ND-6013 Firmware Rev C4.60
1. Only open channel one and disable the other two channels.
2. Disable open detect function.
3. Select the correct input range, different input range have different
apply calibration resistances.
4. Apply the correct offset resistance to channel 0, detail resistance
value, see table 5-2.
5. Send
“Offset Calibration $(Addr)1” to analog input module five
times.