Specifications—units with electric heater i – Bryant 517G User Manual
Page 5
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
SPECIFICATIONS—UNITS WITH ELECTRIC HEATER
I
MODEL
517G
SIZE
H048020
P0480Z5H
P048030I
I N060075 I N060010 I P060010 I N060012
1 RATINGS & PERFORMANCE
Nominal Capacity (Btuh)*
48,000
48,000
48,000
60,000
60,000
60,000
60,000
Nominal Airflow (FF/Min)t
1600
1600
1600
2000
2000
2000
2000
Electric Heating Output (KW)t
20.0
25.0
30.0
7.5
10.0
10.0
12.0
Electric Heating Capacity (MBtuh)f:
51.3/62.7
64.1/78.4
76.9/86.0
19.2/23.5
25.6/31.3
25.6/31.3
30.8/37.6
1 ELECTRICAL ^
Unit Volts-Phase (60 Hz)
208/230-1
208/230-3 1 208/230-1 ■
208/230-3 1 208/230-1B
208/230-1
208/230-1
208/230-3
208/230-1
Operating Voltage Range
187-253
187-253
187-253
187-253
187-253
187-253
187-253
Internal Circuit Protection**
Fuses
CBtt
Fuses
Fuses
None
None
ICBtt
None
Fuses
Single-Circuit Operation
Rated Load Amps
76.8/84.8
_
56.8/62.5
94.8/104.8
67.2/74.1
112.8/124.8
32.6/35.6
41.6/45.6
26.4/28.6
49.0/53.6
Minimum Ampacity for Wire Sizing
97/107
-
72/79.1
119.5/132
85/93.6
142/157
40.8/44.5
52/57
33/35.75
61.25/67
Minimum Wire Size***
3/2
—
4/4
1/0
3/3
0/00
8/8
6/6
8/8
6/4
Maximum Wire Length (Ft)***
119/151
—
156/157
154/194
167/168
163/205
90/91
110/111
.136/139
93/149
Maximum Fuse Size (Amps)
100/110
—
80/80
125/150
90/100
150/175
45/45
60/60
35/40
70/70
Dual-Circuit Operation
Rated Load Amps L1 & L2
40.8/44.8
_
_
_
_
_
34.5/37.6
L3&L4
36/40
_
-
-
-
14.5/16
Minimum Ampacity for Wire Sizing
L1 & L2
52/57
_
_
_
_
_
43.1/47
L3&L4
45/50
-
_
—
—
-
18/20
Minimum Wire Size*** L1 & L2
6/6
-
-
-
—
-
.
8/6
L3&L4
8/6
-
_
-
-
-
12/12
Maximum Wire Length (Ft)*** Lt &L2
112/113
-
-
_
-
-
85/135
L3&L4
81/126
_
-
-
_
80/80
Maximum Fuse Size (Amps) L1 & L2
60/60
-
-
- ■
-
—
45/50
L3&L4
45/50
-
-
-
—
20/20
Control Transformer—24V (VA)
60
60
60
60
60
60
60
INDOOR COIL .
Rows & Fins Per Inch
3&.13
4 & 1 2
Height X Width (In.)
32.5 x22.8
32.5 x22.8
Face Area (Sq Ft)
5.1
5.1
R-22 Refrigerant Metering Device
Check-Flo-Rater
Check-Flo-Rater
Piston ID Number
82
88
Condensate Drain Connection (Pri-Sec)
3/4 MPT-3/4 FPT
3/4 MPT-3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.)
1 0 x 9
1 1 x 9
Filter Size—Cleanable (In.)
2 0 x 2 5 x 1
2 0 x 2 5 x 1
Blower Motor HP
1/2
3/4
Blower Motor Speeds & Type
3 & DD(PSC)
3 & DD(PSC)
Rated Load Amps
4.8
5.6
OPTIONAL EQUIPMENT (P/N’S)
I
Liquid-Tube Swivel Ell (3/8)tt
P651-1066
P651-1066
Vapor-Tube Swivel Ell (3/4)t1:
P651-1068
P651-1068
Single-Circuit Kit**
301802-4001 1 1 =
T 1 1 = |301820-4001
*See condensing unit or heat pump section PDS for cooling and/or heating capacity ratings with 517G Fan Coils.
tSee air delivery table in this PDS.
$KW values shown are nominal rated heater outputs at 240V and do not include blower motor heat. Capacity values shown are calculated using KW
outputs at 208V/230V.
**Single-phase 10-, 15-, or 20-KW electric heaters have the internal circuit protection options shown. Single-phase 12-, 15-, or 20-KW heaters are
wired for dual-circuit operation. The optional single-circuit kit may be field-installed in units with a 12-, 15-, or 20-KW single-phase fused heater for
single-circuit operation.
ttCB = circuit breakers.
ttUsed for right-angle refrigerant connections to the coil.
***Wire sizes and lengths are based on copper conductor at 86 ° F (30 ° C) ambient temperature and ampacity shown in table. Insulation must be 90 ° C
on conductor used between the disconnect switch and thé heater and at least 75 °C on the conductor used between the disconnect and the serv
ice panel. If other than copper conductor is used, or if ambient temperature is above 86 ° F, determine wire size for ampacity shown and the National
Electric Code. Wire lengths shown are measured one way along the wire path between the disconnect and service panel for minimum 2%
voltage drop.
■Units with 25- and 30-KW electric heaters are wired for 3-phase operation. These units are field-convertible for single-phase operation by moving
two factory high-voltage wires.