Specifications—units with electric heater – Bryant 517G User Manual
Page 4
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
SPECIFICATIONS—UNITS WITH ELECTRIC HEATER
MODEL
517G
SIZE
N048075 I N 0 4 8 0 1 0
P048010
N048012
N048015
P048015
P048018
1 RATINGS & PERFORMANCE
Nominal Capacity (Btuh)»
48,000
48,000
48,000
48,000
48,000
48,000
, -48,000
Nominal Airflow (Fts/Min)t
1600
1600
1600
1600
1600
1600
1600
Electric Heating Output (KW)t
7.5
10.0
10.0
12.0
15.0
15.0
18.0
Electric Heating Capacity (MBtuh)t
19.2/23.5
25.6/31.3
25.6/31.3
30.8/37.6
38.5/47.0
38.5/47.0
46.1/56.4
1 ELECTRICAL
Unit Voits—Phase (60 Hz)
208/230-1
208/230-1
208/230-3
208/230-1
208/230-1
208/230-3
208/230-3
Operating Voltage Range
187-253
187-253
187-253
187-253
187-253
187-253
187-253
Internal Circuit Protection»»
None
None 1 CBtt
None
Fuses
Fuses
CBtt
None
None
Single-Circuit Operation
Rated Load Amps
31.8/34.8
40.8/44.8
25.6/27.6
48.2/52.8
58.8/64.8
36.0/39.5
42.4/46.4
Minimum Ampacity for Wire Sizing
40.8/44.5
52/57
33/35.75
61.25/67
74.5/82
46/50.4
54/59
Minimum Wire Size»»»
8/8
6/6
8/8
6/4
6/4
_
6/6
6/6
Maximum Wire Length (Ft)»»»
92/93
112/113
140/144
95/151
78/123
—
156/157
132/134
Maximum Fuse Size (Amps)
45/45
60/60
35/40
70/70
80/90
—
50/60
60/60
Dual-Circuit Operation
Rated Load Amps LI & L2
33.7/36.8
40.8/44.8
L 3 & L 4
—
—
—
14.5/16
18/20
—
Minimum Ampacity for Wire Sizing
LI &L2
43.1/47
52/57
L3 & L4
—
—
-
18/20
22.5/25
—
Minimum Wire Size»»» LI. & L2
—
—
—
8/6
6/6
L 3 & L 4
-
-
—
12/12
10/10
—
—
Maximum Wire Length (Ft)»»» LI & L2
—
—
—
87/137
112/113
—
—
L 3 & L 4
—
—
_
80/80
102/102
_
—
Maximum Fuse Size (Amps) LI & L2
—
—
45/50
60/60
—
■ —
L 3 & L 4
—
—
—
20/20
25/25
—
—
Control Transformer—24V (VA)
60
60
60
60
60
60
60
INDOOR COIL
Rows & Fins Per Inch
3 & 1 3
Height X Width (In.)
3 2 . 5 x 2 2 . 8
Face Area (Sg Ft)
5.1
R-22 Refrigerant Metering Device
Check-Flo-Rater
Piston ID Number
82
Condensate Drain Connection (Pri-Sec)
3/4 MPT-3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.)
1 0 x 9
Filter Size—Cleanable (In.)
20 X 25 X1
Blower Motor HP
1/2
Blower Motor Speeds & Type
3 & DD(PSC)
Rated Load Amps
4.8
OPTIONAL EQUIPMENT (P/N’S)
Liguid-Tube Swivel Ell (3/8)tt
P651-1066
Vapor-Tube Swivel Ell (3/4)tt
P651-1068
Single-Circuit Kit»»
1 1 i 301820-4001
\
= 1
»See condensing unit or heat pump outdoor section PDS for cooiing and/or heating capaoity ratings with 517G Fan Coils.
fSee air delivery table in this PDS.
tKW values shown are nominal rated heater outputs at 240V and do not include blower motor heat. Capacity values shown are calculated using KW
outputs at 208V/230V.
»»Single-phase 10-, 15-, or 20-KW electric heaters have the internal circuit protection options shown. Single-phase 12-, 15-, or 20-KW heaters are
wired for dual-oirouit operation. The optional single-circuit kit may be field-installed in units with a 12-, 15-, or 20-KW single-phase fused heater for
single-circuit operation.
ttCB = circuit breakers.
ttUsed for right-angle refrigerant connections to the coil.
»»»Wire sizes and lengths are based on copper conductor at 86 ° F (30 ° C) ambient temperature and ampacity shown in table. Insulation must be 90 ° C
on conductor used between the disconnect switch and the heater and at least 75 “ C on the conductor used between the disconnect and the serv
ice panel. If other than copper oonductor is used, or is ambient temperature is above 86 °F, determine wire size from ampacity shown and the Na
tional Electrical Code. Wire lengths shown are measured one way along the wire path between the disoonnect and service panel for minimum 2%
voltage drop.
SSC-68