Bryant Model 516 User Manual
Page 2
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
T O P V I E W
S I D E V I E W
10
D
o o
«i
Electric Duct Heater Dimensional Drawing
TABLE I - RATINGS AND CAPACITIES
Packoge
P/N
KW
Rating
* Capacity Btuh
Field Wire Connections
No. of
Circuits
Minimum Wire Size
AWG - 90° C - Copper
Max Fuse Size
Amps
208 V
230V
240V
65901D03
3
7,690
9,403
10,239
1
12
(2) 20
65901D04
4
10,254
12,538
13,652
1
10
(2) 20
65901D05
5
12,817
15,672
17,065
1
10
(2) 30
65901D06
6
15,381
18,807
20,478
1
10
(2)40
65901D07
7
17,944
21,941
23,891
1
8
(2) 50
65901D08
8
20,508
25,076
27,304
1
8
(2) 50
65901D09
9
23,071
28,210
30,717
1
6
(2) 60
65901D010
. 9 . 6
24,610
30,091
32,764
1
6
(2) 60
65901D011
11
28,199
34,479
37,543
2
10
** (2) 30
10
(2) 40
65901D012
12
30,762
37,614
40,956
2
10
** (2) 30
8
(2) 50
6590IDO13
13
33,326
40,748
44,369
2
10
** (2) 30
8
(2) 50
6590IDO14
14
35,889
43,883
47,782
2
10
** (2) 30
8
(2) 50
65901D015
14.4
36,915
45,136
49,147
2
10
** (2) 30
8 -
(2) 50
* Rated at 240V, 60 cycle, single phase
** Includes blower motor and one heating element
39516D3