Installation Instructions

ELECTRIC DUCT HEATER PACKAGE

516

b Pliant

These instructions are to be used in con­
junction with the basic instructions for the

Model 516 Fan Coil Unit. Section II of this
instruction describes the installation of the
electric duct heater package with other than

the Model 516 air handlers .

SECTION I

The electric duct heater is designed to be

used with the Models 18- and 24-516 Fan Coil
Units. Refer to Table I, Ratings and Capaci­
ties, for sizes and power inputs. Refer also

to the Dimensional Drawing.

The package, as shipped from the factory,

contains heater coils, a rating plate, a

sequencing relay (for 11- through 14,4-KW
size units), automatic temperature control,

and a manual temperature control switch.

Each heater has both sides of the power line

broken by a main contactor and a backup

contactor, and has an open set of contacts for

fan control.

Before Starting Installation:

1. Check local codes and ordinances for ad­
ditional requirements.

2. Check the incoming power supply to be
sure that the rated voltage, frequency, and

phase correspond to that stamped on the unit

ratirig plate.

3 . Check the building power supply to be sure

that it is sufficient to handle the additional
electrical load imposed by this equipment.

Installing the Electric Duct Heater Package

The duct heater package is designed for zero
clearance from combustible material. There
must be a 7 -1 /2 inch clearance in front of the
control box cover.

A collar for mounting the duct heater is pro­

vided with each Fan Coil Unit. Use this collar

I

39516D3

5/1/69

if the heater is to be installed within 6 inches
downstream from the Fan Coil. Mount the
collar on the duct flanges of the Fan Coil so

that the opening for the duct heater is on the

same side of the Fan Coil as the coil con­
nections and rating plate. Make certain that

the flange is at the bottom of the duct heater

opening. This will insure that the heater is

placed at the correct depth.

Now, place the heater into the collar and
attach it to the collar with four sheet metal

screws.

If the application does not provide adequate

space for the duct heater to be installed
6 inches from the Fan Coil, then the duct

heater must be installed 48 inches down­

stream from the Fgyj-Coil Unit-.

To install the he,

from the Fan Co
hole in the side
heater into place

template, drill fo|.r_moun
the heater with

An air filter mi
airstream.

es .downstream

8 inch
de the

Ox as a

attach

crews.

return