Fig. 9—decorative backplate assembly, Fig. 10—4–wire abcd connector, Fig. 11—functional overview – Carrier Infinity SYSTXCCUID01 User Manual
Page 4: Fig. 12—universal four-wire connection diagram, User interface, Spd. ac or hp, Variable-speed furnace/ fan coil
![background image](/manuals/720691/4/background.png)
ELECTRICAL OPERATION HAZARD
Failure to follow this caution will result in equipment damage
or improper operation.
Improper wiring of the ABCD connector will cause the
Infinity Control™ to operate improperly. Check to make sure
all wiring is correct before proceeding with installation or
turning on power.
9. Push any excess wire into the wall. Seal hole in wall to prevent
any air leaks. Leaks can affect operation.
10. Attach Infinity Control™ to the mounting plastic by lining up
the plastic guides on the back of the control with the opening
on the mounting plastic and push on.
11. Perform installation of all other system equipment (i.e. hu-
midifier, ventilator, UV lights, etc.)
12. Turn on power to equipment.
EQUIPMENT WIRING DIAGRAMS:
See wiring diagram Figs. 12, 13 and 14.
NOTE:
For other applications not listed, refer to the Network
Interface Module (NIM) Installation Instructions.
See wiring diagram figure 12 for a Typical Four-Wire Connection
Diagram, which includes an Infinity indoor communicating fur-
nace or FE fan coil with a 2-speed Puron® communicating outdoor
unit. No additional OAT (outdoor air temperature) sensor is
required because the Infinity Control will use the temperature
sensor inside the 2-speed unit.
See wiring diagram figure 13 for a Typical Connection Diagram,
which includes an Infinity indoor communicating furnace or FE
fan coil, with a 1-speed air conditioning unit (non-communicating
outdoor). An Outdoor Air Temperature sensor may be installed
(not required) at the indoor furnace or fan coil OAT terminals.
When OAT is applied, the Infinity System will provide full system
features and benefits.
See wiring diagram Fig. 14 for a Typical Connection Diagram for
FE fan coil with a 1-speed heat pump (using non-communicating
outdoor unit). When OAT is applied, the Infinity System will
provide full system features and benenfits.
HUMIDIFIER CONNECTION — A 24vac bypass or fan
powered humidifier may be installed.
NOTE:
Do Not Use a traditional humidistat to control humidifier
operation. If a humidifier is installed, let the Infinity System
control humidifier operation.
Bypass Humidifiers — A bypass humidifier should be wired
directly to the furnace or fan coil HUM and 24vac COM terminals.
The Infinity Control will automatically energize the HUM output
during a call for humidification.
Fan Powered Humidifiers — Most fan powered humidifiers
produce internal 24vac in order to energize upon a switch or
contact closure. For this application, a 24vac N.O. Isolation Relay
(DPST) MUST be used to prevent mixing the internal humidifier
power with the indoor equipment transformer. Applying 24vac
isolation relay coil to furnace or fan coil HUM and COM terminals
will allow the Infinity Control to automatically energize the HUM
output during a call for humidification. The N.O. relay contacts
will be used to energize the humidifier. See fan powered humidi-
fier installation instructions for more details.
Fig. 9—Decorative Backplate Assembly
A03192
Fig. 10—4–Wire ABCD Connector
A03193
A
B
C
D
Fig. 11—Functional Overview
A03194
HOLD
COOL
HEAT
SCHEDULE
VACATION
PROGRAM
SCROLL
BASIC
ADVANCED
SETUPS
Schedule
to program
temperature
schedule
Vacation
to start/end
vacation
Basic
to set time,
humidity
Advanced
for all other
settings
Scroll
up & down
Fan Button
Display Screen
(LCD)
Right-Side
Button
Heat Button
Cool Button
Temperature
(+/-) Button
System
On/Off Button
Basic & Advanced
Setup Buttons
Flip Down
Door
Left-Side
Button
Humidity/OAT
Button
Hold
Button
Time (+/-)
Button
Schedule & Vacation
Program Buttons
Up/Down
Scroll Buttons
A
B
C
D
A
B
C
D
User Interface
Green
Yellow
White
Red
OAT
Optional Remote
Room Sensor
HUM
COM
24V
Humidifier
Connection
S2
S1
A
B
C
D
ABCD
Connections
2-Spd. AC or HP
Green
Yellow
White
Red
OAT
Sensor
(Optional)
Variable-Speed
Furnace/ Fan Coil
Fig. 12—Universal Four-Wire Connection Diagram
A03146
4