Figure 10 — Adjusting Valve Clearance

ALLEN WRENCH

LOOSEN

JAM NUT

2. When valve clearance is correct, hold the pivot ball stud

with the alien wrench and tighten the rocker arm jam nut

with a crows foot. Tighten the jam nut to 65-85 inch-

pounds torque. After tightening the jam nut, recheck valve

clearance to make sure it did not change (Figure 11).

Figure 11 — Tightening Jam Nut

OUT OF SERVICE PROTECTION

If you cannot exercise the generator every seven

days and it is to be out of service longer than 30 days,
prepare the generator for storage as follows:

• Start the engine and let it warm up.

• While the engine is stili warm from running, drain the oil

completely. Refill crankcase with recommended oil. See

“Specifications."

• Attach a tag to the engine indicating the viscosity and

classification of the oil in the crankcase.

• Remove spark plug and add about 1/2 ounce (15ml) of

clean, fresh engine oil into spark plug threaded opening.

Crank engine several times to distribute oil, then install

and tighten spark plug.

• Remove the battery and store in a cool, dry room on a

wooden board. Never store the battery on any concrete

or dirt floor.

• Clean and wipe the entire generator.

RETURN UNIT TO SERVICE

AFTER STORAGE

To return the unit to service after storage, proceed as
follows:

• Check tag on engine for oil viscosity and classification.

Verify that the correct recommended oil is used in engine.

If necessary, drain and refill with proper oil.

• Check battery. Fill all cells to the proper level with distiiled

water. DO NOT USE TAP WATER IN THE BATTERY.

Recharge battery to 100% state of charge, or, if defective,

replace the battery.

• Turn OFF all electrical loads, then start the engine.

• Let engine warm up.

• Apply electrical loads to at least 50% of the unit’s rated

wattage capacity.

• When engine is thoroughly warmed up, shut it down.

THE GENERATOR IS NOW READY FOR SERVICE.

MAJOR SERVICE MANUAL

To obtain a service manual for your generator, order it
from your dealer/distributor or contact the factory. Be
sure to identify your unit’s MODEL NUMBER and

SERIAL NUMBER.

EXERCISING THE GENERATOR

Generac recommends that you start and operate the
generator at least once every seven days. Let the unit
run for at least 30 minutes to “exercise” the engine.