1 post installation tests, 2 before initial start-up, 3 initial start – Generac 02010-1 User Manual
Page 38: 4 testing under load, Post installation tests, Before initial start-up, Initial start, Testing under load
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
POST-1
INSTALLATION
START-UP
ADJUSTMENTS
Section 3 - Post-installation Start-up Adjustments
PRIMEPACT 50 Recreational Vehicle Generator
3.1
POST INSTALLATION TESTS
The air-cooled generator set was factory tested and
adjusted. You should not be required to adjust the
unit any further except under special circumstances.
-A
WARNING
A-
A
D
o
not make any unnecessary adjustments.
Factory settings are correct for most applica
tions. When making adjustments, however, be
careful to avoid overspeeding the engine.
3.2
BEFORE INITIAL START-UP
Before starting, complete the following:
1. Check the engine crankcase oil level and, if nec
essary, fill to the dipstick “FULL’ mark (cross-
hatched area) with the recommended oil. Do not
fill above the FULL mark.
2. Check the fuel supply. Gas fuel lines must have
been properly purged and leak tested in accor
dance with applicable fuel codes. All fuel shutoff
valves in the fuel supply lines must be open.
-A
DANGER
A
If a liquid propane (LP) gas fuel system has
been installed, it must be properly tested for
leaks before operating the system in compli
ance with ANSI A119.2/NFPA 501C. No leakage
is permitted. You must be sure no gasoline fuel
vapors enter the vehicle interior.
3.3
INITIAL START
When you are absolutely certain that the unit has
been properly installed and prepared for use, start
the engine as follows:
1. Turn off all electrical loads. Do this by setting the
generator’s main circuit breakers to their “OFF”
(or open) position.
2. Refer to Part I, Section 2.5, “Starting the
Generator” (Page 8), for cranking and starting
instructions. The engine may require more
cranking for initial starting since the fuel lines
have to be primed (use of the primer switch will
shorten this time).
3. Let the engine warm up for about five minutes to
allow internal temperatures to stabilize.
4. Carefully inspect the engine/generator for fuel, oil
and exhaust system leaks. Before proceeding to the
next step, correct any leakage immediately.
5.
When all tests and adjustments at no-load are
completed, apply electrical loads and check for
proper operation under load. See Section 3.4.
Run the unit at least 30 minutes with loads
applied.
6. Turn off all electrical loads by setting the genera
tor’s main circuit breakers to their “OFF" (or
open) position.
7.
Let the unit run at no-load for a few minutes to
stabilize Internal engineZ-generator temperatures.
Then, shut down the engine.
NOTE:
The
generator
set
was
thoroughly
tested
and
adjusted at the factory before shipping. No addi
tional adjustment should be necessary. Only qual
ified service technicians who have been trained
should perform adjustments outlined in this man
ual.
3.4
TESTING UNDER LOAD
Apply electrical loads equal to about 75 to 100 per
cent of the unit's rated wattage/amperage capacity.
Let the unit run at least 30 minutes with load applied.
During this part of the test, check that the unit is not
running excessively hot and that adequate cooling air
flow is available. You must not allow the unit to over
heat during prolonged operation.
NOTE:
The generator engine is equipped with
a
high tem
perature switch. The switch has normally closed
(N.C.) contacts. When the engine temperature is
too high, switch contacts close, and the engine
shuts down automatically.
GENERAC RECOMMENDS THAT YOU TEST THE
GENERATOR FOR ADEQUATE COOLING.
36 Generao® Power Systems, Inc.