INSTALLATION
Section
2
-
Installation
PRIMEPACT 50 Recreational Vehicle Generator
The greater the airflow through the carburetor ven
turi, the lower the pressure at the venturi throat. The
lower the pressure at the venturi throat, the greater
the diaphragm movement, and the greater the move
ment of the regulator valve. The more the regulator
valve opens, the greater the gas flow that is propor
tional to airflow through the generator.
The following facts about the secondary regulator
must be emphasized:
• The regulator must be sensitive to venturi throat
pressure changes throughout the operating range.
• The regulator must be properly adjusted so it will
stop the flow of gas when the engine is not running
(no air flow through the carburetor).
• The slightest airflow (and vacuum in the venturi
throat) should move the regulator valve off its seat
and permit gas to flow.
•
2.5.6 FUEL SUPPLY LINES_________________________
• LP gas lines must be accessible, but protected
against possible damage.
• Do NOT connect electrical wiring to any LP gas fuel
line or run wiring alongside the lines.
• Route gas lines away from hot engine exhausts.
• Retain gas lines with metal clamps that do not have
sharp edges.
• Install an approved length of flexible hose between
the gaseous fuel solenoid valve and rigid fuel sup
ply lines. The flexible line must be nonmetallic,
nonorganic
and
nonconductive.
It
must
be
approved for use with LP gas.
•
2.5.7 EXCESS FLOW VALVE
LP gas tanks should have an excess flow valve,
according to NFPA .50
1C,
Paragraph 3-4.4. This valve
and the gas lines must be carefully sized so the valve
will close when a fuel line is severed or broken.
Consult the Natural-LP Gas Association for informa
tion and limitations of excess flow valves.
Manual shutoff valves on the supply tank and else
where in the system must be fully open when operat
ing the generator. The excess flow valve functions
properly only if all valves are fully open.
•
2.5.8 LEAKAGE TESTS____________________________
Do not place the generator into service until you have
properly tested the gas system for leaks. To test the
system, you need a separate source of 12 volts DC to
open the gaseous fuel solenoid valve.
The leak test must comply fully with NFPA,
Paragraph 318. All connections, hoses, valve regula
tors, fittings, and other fuel system parts must be
tested under gas or air pressure of not less than 90
psi (620 kPa), while using soap and water or an
equivalent solution to check for leaks. Other
approved methods of testing for leaks may be used, if
appropriate. DO NOT USE ANY FLAME TO TEST
FOR LEAKS.
DANGER
A
Gaseous fuel lines between the tank and the
secondary regulator are under a positive pres
sure (about 11 inches water column). Gas pres
sure at the outlet side of the secondary regula
tor, however, is a negative pressure and can
draw flame inside a line or fitting and cause an
explosion.
2.6
EXHAUST SYSTEM
The generator exhaust system must be safely and
properly installed. Only approved mufflers and other
exhaust system parts must be used. A properly
installed exhaust system must be vapor tight, quiet
and completely safe.
DANGER
The generator engine gives off DEADLY carbon
monoxide gas through its exhaust system. This
dangerous gas, if breathed in sufficient concen
trations, can cause unconsciousness or even
death. Never operate the generator set with
the vehicle inside any garage or other enclosed
area. DO NOT OPERATE THE GENERATOR IF THE
EXHAUST SYSTEM IS LEAKING OR HAS BEEN
DAMAGED. SYMPTOMS OF CARBON MONOX
IDE POISONING ARE
(a)
inability to think coher
ently; (b) vomiting; (c) twitching muscles; (d)
throbbing temples; (e) dizziness; (f) headaches;
(g) weakness; and (h) sleepiness. IF YOU FEEL
ANY OF THESE SYMPTOMS, MOVE INTO FRESH
AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET
MEDICAL HELP. Do not operate the generator
until its exhaust system has been inspected and
properly repaired.
---------
M.
CAUTION ----------------------
Never tee the generator engine exhaust pipe
into the vehicle engine exhaust piping. This
causes excessive back pressure on the genera
tor engine. Also, water from one engine can
damage the other engine.
30 Generac® Power Systems, Inc.