beautypg.com

Carrier WEATHERMAKER ZONEKIT2ZCAR User Manual

Page 3

background image

2. Properly seal joint using duct tape, mastic, or other approved

method. Do not allow mastic to come in contact with actuator.

3. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check

your local codes.) (See Fig. 7.)

NOTE:

All zone dampers and ductwork must be properly sup-

ported according to local codes or SMACNA standards.

NOTE:

There should be a minimum of 4 ft between the zone

damper and the first branch duct if more than 1 branch duct is
downstream of the zone damper.

ROUND FLEXIBLE DUCTWORK

1. Slip 1 end of flexible ductwork over 1 end of zone damper.

(See Fig. 8.)

2. Secure the flexible duct to zone damper using SMACNA or

other approved method.

3. Properly seal joint using duct tape, mastic, or other approved

method. Do not allow mastic to come in contact with actuator.

4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check

your local codes.) (See Fig. 9.)

NOTE:

All zone dampers and ductwork must be properly sup-

ported according to local codes or SMACNA standards.

RECTANGULAR FIBROUS GLASS DUCTWORK

1. Insert 1 end of zone damper into 1 end of fibrous glass

ductwork approximately 2 to 3 in. (See Fig. 10.)

2. Screw field-supplied screws and tabs into zone damper.

3. Properly seal joint using duct tape, mastic, or other approved

method. Do not allow mastic to come in contact with actuators

4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check

your local codes.) (See Fig. 11.)

Fig. 5—Insulated Round Metal Ductwork

A95130

/

STEEL STRAP

1

2

Fig. 6—Rectangular Metal Ductwork

A92478

DRIVE

ZONE
DAMPER

S-LOCK

SUPPLY
AIR DUCT

Fig. 7—Insulated Rectangular Metal Ductwork

A95131

1 / " TO 2"

INSULATION

1 2

Fig 8—Round Flexible Ductwork

A95132

FLEXIBLE

DUCT

ZONE

DAMPER

Fig. 9—Insulated Round Flexible Ductwork

A95133

/

STEEL STRAP

1 2

Fig. 10—Rectangular Fibrous Glass Ductwork

A92480

ZONE
DAMPER

2

TO 3

FIBROUS
GLASS
DUCTWORK

FIELD
SUPPLIED
SCREWS

Fig. 11—Insulated Rectangular Fibrous Glass

Ductwork

A95134

1 /

TO 2

INSULATION

1 2

3